LoRaWAN MC-LW-FCT-01 MClimate Fan Coil Thermostat User Manual
Mode selection
By default, the device supports 3 operating modes - heating/cooling/ventilation. Depending on the wiring diagram
of the Fan Coil Unit, some modes might be disabled by default. E.g. if you are using a 2-pipe fan coil unit, it can
either heat or cool, it cannot do both throughout the whole year. In this case, short-pressing the ON/OFF/MODE
button will switch between heating/ventilation or cooling/ventilation, depending on the current allowed
operational modes. If you are using a 10k NTC connected to IO1 and IO2, the FCT will determine the allowed
operational modes independently based on whether the system is circulating hot or cold water.