Honeywell TH6320ZW2003 Pro Z-Wave Programmable Thermostat Installation Guide

# ISU  
ISU Name  
ISU Options (defaults in bold)  
Notes  
256  
EM Heat Type  
Electric, Gas/Oil (or Fossil Forced Air)  
This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1 AND if ISU 253  
is set to run AUX/E heat separately.  
260  
300  
Fossil Kit Control  
Auto Changeover  
Thermostat, External (Fossil Fuel Kit Controls Backup Heat)  
This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1, AND if ISU 256  
is set to Gas/Oil.  
On, Off  
OFF: The user must select heating or cooling as needed to maintain the desired indoor temperature.  
ON (Automatic): On (enabled) Allows user to select Auto Changeover as one of the system modes from the  
home screen. In auto mode, the thermostat control either heating or cooling automatically to maintain the  
desired indoor temperature.  
Default setting varies depending on manufacture date  
303  
Auto Differential  
0 °F to 5 °F or 0.0 °C to 2.5 °C  
Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential  
setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat  
or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous  
thermostats.  
Default setting varies depending on manufacture date  
305  
306  
340  
High Cool Stage  
Finish  
Yes, No  
This ISU is only displayed when the thermostat is set to 2 cool stages. When set to YES, this feature keeps the  
higher stage of the cooling equipment running until the desired setpoint is reached.  
High Heat Stage  
Finish  
Yes, No  
This ISU is only displayed when the thermostat is set to 2 or more heat stages. When set to YES, this feature  
keeps the higher stage of the heating equipment running until the desired setpoint is reached.  
Aux Heat Droop  
0 = Comfort; 2 °F to 15 °F from setpoint (in 1 °F increments)  
or 1.0 °C to 7.5 °C from setpoint (in 0.5 °C increments)  
Aux heat droop can be set on heat pump systems with an auxiliary heat stage. The Comfort setting is NOT  
available for Dual Fuel systems. Default setting is 0 °F (Comfort) for Electric while 2 °F for Gas/Oil. The indoor  
temperature must drop to the selected droop setting before the thermostat will turn Aux Heat on. For example,  
if Aux Heat is set to 2 °F (1.0 °C), the indoor temperature must be 2 ° F (1.0 ° C) away from the setpoint before  
Aux Heat turns on. When set to Comfort, the thermostat will use Aux Heat as needed to keep the indoor tem-  
perature within 1 °F (0.5 ° C) degree of the setpoint.  
350  
355  
Up Stage Timer Aux  
Heat  
Off, 30, 45, 60, 75, 90 minutes  
2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours  
The Auxiliary Heat Upstage Timer starts when the highest stage of the previous heating equipment type turns  
on. Auxiliary heat will be used (if needed) when the timer expires. This ISU is only displayed when ISU 340 (AUX  
Heat Droop) is set to 2 °F or higher.  
Balance Point  
(Compressor  
Lockout)  
Off, 5 °F to 60 °F (in 5 °F increments) or 15.0 °C to 15.5 °C  
(in 2.5 °C or 3.0 °C increments)  
Compressor Lockout requires an outdoor temperature. Set Compressor Lockout to the temperature below  
which it is inefficient to run the heat pump. When outside temperature is below this setting, thermostat will  
lockout the heat pump and run Aux Heat only. This ISU is only displayed if ISU 130 = Wired, ISU 200 is set to  
Heat Pump, ISU 221 Aux/E stages = 1. Default is 40 °F if ISU 205 Heating Equipment is Air to Air Heat Pump  
and ISU 255 Aux Heat Type is Gas/Oil. Default is Off if ISU 205 Heating Equipment is Air to Air Heat Pump and  
ISU 255 Aux Heat Type is Electric. Default is Off if ISU 205 Heating Equipment is Geothermal. Compressor  
Lockout is optional for any type of heat pump (Air to Air Heat Pump, Geothermal Heat Pump).  
356  
Aux Heat Lock Out  
(Aux Heat Outdoor  
Lockout)  
Off, 5 °F to 65 °F (in 5 °F increments) or  
-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)  
Aux Heat Lockout requires an outdoor temperature. Set Aux Heat Lockout to optimize energy bills and to not  
allow to run the more expensive Aux Heat source above certain outdoor temperature limit. This ISU is only  
displayed if ISU 130 = Wired, ISU 200 is set to Heat Pump, ISU 221 Aux/E stages = 1.  
GeneralDetails
NameHoneywell TH6320ZW2003 Pro Z-Wave Programmable Thermostat Installation Guide
MakeHoneywell
LanguageEnglish
FiletypePDF (Download)
File size2.34 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TL116A Thermostat Installation Guide
Honeywell TL116A Thermostat Installation Guide
T10 Pro Smart Thermostat with Redlink Room Sensor
T10 Pro Smart Thermostat with Redlink Room Sensor
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell RTH2300 Thermostat User Guide
Honeywell RTH2300 Thermostat User Guide

Honeywell TH6320ZW2003 Pro Z-Wave Programmable Thermostat Installation Guide