HELTUN Fan Coil Thermostat HE-FT01 User Manual
SmartStart
SmartStart-enabled products can be added to a Z-Wave network
by scanning the Z-Wave QR Code shown on the product with
gateways/controllers that allow for SmartStart inclusion. In this
case, no further action will be required and the SmartStart product
will be added automatically within ten minutes of being turned on in
the vicinity of a network.
To add the HE-FT01 to a Z-Wave network using SmartStart:
1. Set the main controller in Security S2 Authenticated “Add Mode”
2. Input the HE-FT01 DSK code to the controller
3. Power on the device.
4. Wait for the Inclusion process to complete.
5. A successful “Add” will be confirmed by display of the Antenna
with signal strength bars ( ) icon in the bottom right corner of
the main screen.
Note: The device DSK and QR code are printed on the HE-FT01 back panel plus on the manual included in the HE-
FT01 packaging.
Firmware OTA Update
To wirelessly update the HE-FT01 firmware, follow these steps:
1. Check the current firmware version in the settings Parameter 13
2. Start the process from the Z-Wave gateway/controller
3. Download the firmware that corresponds to the HE-FT01.
4. Set the main controller in Firmware OTA (“over-the-air”) Update Mode (see gateway/controller manual).
5. As soon as Firmware update begins, “LOAd” text will be displayed on the screen (this will take a few minutes).
6. When the Firmware has updated, “UPd” will display on the screen for three seconds and the HE-FT01 will reboot.
7. When the update has completed, the HE-FT01 will return to normal operation.
8. If desired, verify the update was successful by checking the firmware version in Parameter 13 of the Settings
Mode.
Associations
Association enables the HE-FT01 to control other Z-Wave devices over the network. An Association Groups may
include up to 50 other devices from different brands and/or manufacturers (10 devices on each group except group 1).
The HE-FT01 has six association groups:
1st Association Group – “Lifeline”: reports the state of the device and is used to communicate with the Z-Wave
gateway. The group supports one Node.
Note: It is not recommended to modify this group.
2nd Association Group – “Fan Low Speed (OUT-1)” is used to turn the associated devices on/off reflecting OUT-1
operation. The group supports one Node.
3rd Association Group – “Fan Medium Speed (OUT-2)” is used to turn the associated devices on/off reflecting
OUT-2 operation. The group supports one Node.
4th Association Group – “Fan High Speed (OUT-3)” is used to turn the associated devices on/off reflecting OUT-3
operation. The group supports one Node.
5th Association Group – “Heater (OUT-4)” is used to turn the associated devices on/off reflecting OUT-4 operation.
The group supports one Nodes.
6th Association Group – “Cooler (OUT-5)” is used to turn the associated devices on/off reflecting OUT-5 operation.
The group supports one Node.
Note: Through Groups 2-6 the HE-FT01 sends Basic Set command with value 0 (Off) when the relay goes to OFF
state and sends 255 (On) when the relay goes to ON state.
14
| General | Details |
|---|---|
| Name | HELTUN Fan Coil Thermostat HE-FT01 User Manual |
| Make | HELTUN |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.35 MB |

HELTUN HE-HT01 Heating Thermostat User Guide