HELTUN Fan Coil Thermostat HE-FT01 User Manual
Climate Control Modes
The current Climate control mode is shown on the middle-right position of the LCD under “OPERATING MODE.”
The HE-FT01 can operate in 4 climate modes:
Icon
Device mode
Mode in Z-Wave gateway
Heating & Cooling
Heating
“Auto Changeover”
“Heat” or “Energy Heat”
“Cool” or “Energy Cool”
“Fan”
Cooling
Ventilation
Change the climate mode by touching the “Climate” button (
) and selecting as shown above.
Heating & Cooling
In this mode, the HE-FT01 switches automatically between heating and cooling states. The primary purpose of
automatic climate control is to manage the temperature of the area to provide maximum comfort. This means the
thermostat will heat the room when the room temperature is lower than the temperature Set Point, and it will cool the
room when room temperature is higher than the Set Point.
Note: This Mode is available only for “COM” and “TIME” Operating Modes.
Note: According to Z-Wave protocol standards, your Z-Wave gateway will show this mode as “Auto Changeover.”
Heating
This mode is used when only heating is needed as in winter. In this mode, when the room temperature is lower than
the Set Point, the thermostat will switch ON the heater (OUT-4 will be ON, OUT-5 will be OFF). When room
temperature goes higher than the Set Point, it will switch to IDLE mode (all five outputs will be OFF).
Note: According to Z-Wave protocol standards, your Z-Wave gateway will show this mode as: 1) “Heat” if you have
selected “COM” Operating Mode, and as 2) “Energy Heat” if you have selected “ECO” Operating Mode.
Cooling
This mode is used when only cooling is needed as in summer. In this mode, when the room temperature is higher
than the Set Point, the thermostat will switch ON the air conditioner (OUT-5 will be ON, OUT-4 will be OFF). When the
temperatures goes lower than the Set Point, the thermostat will goes to IDLE mode (all five outputs will be OFF).
Note: According to Z-Wave protocol standards, your Z-Wave gateway will show this mode as: 1) “Cool” if you have
selected the “COM” Operating Mode, and as 2 “Energy Cool” if you have selected “ECO” Operating Mode.
Ventilation
In Ventilation mode the thermostat circulates air around the room without heating or cooling (heating and cooling
valves are closed: OUT-4 and OUT-5 will be always OFF).
Note: when in Ventilation mode, all Operating Modes (COM, TIME, ECO) are disabled and "OFF" will be displayed
under "SET TEMP" on the LCD.
Note: According to Z-Wave protocol standards your Z-Wave gateway will show this mode as “Fan.”
Fan Speed Modes
The HE-FT01 has six fan speeds:
Low speed
Medium speed
High speed
Auto Medium speed
Auto High speed
OFF
In Low, Medium, and High speeds, the thermostat always runs the selected speed (OUT-1 will be ON in case if Low
speed is selected, OUT-2 will be ON for Medium speed, OUT-3 will be ON for High speed).
7