Parameter 33 – Air Temperature Sensors Report Threshold  
This parameter determines the change in temperature level (in °C) resulting in temperature sensor reports being sent  
to the gateway. The value of this parameter should be x10, e.g. for 0.4°C, use the value “40.” You may select from  
0.5°C to 10°C. Use the value “0” if you need to stop sending the reports. The factory-default value is 0.5°C (5).  
Parameter 34 – Humidity Sensor Report Threshold  
This parameter determines the percentage change in relative humidity level which will trigger a report being sent to  
the gateway. From 2% to 25% can be selected. Use the value “0” if there is a need to stop sending the reports. The  
factory-default value is 2.  
Parameter 35 – Light Sensor Report Threshold  
This parameter determines the change in the ambient illumination level that will trigger a report being sent to the  
gateway. From 10% to 99% can be selected. Use the value “0” if there is a need to stop sending the reports. The  
factory-default value is 50.  
Parameters 36-40 – Relays load power in watt.  
It is possible to specify the consumption of the loads in watts for each relays channel.  
The device will calculate total consumption relative to the time, during which the output of the relays is in the ON state.  
Factory default value: 0  
Parameter 41 – TIME mode operation  
This parameter determines the Climate Mode (Heating or Cooling) to which HE-FT01 will switch when the TIME  
operating mode is selected. If the value = 1 the thermostat will go to Heating & Cooling mode, if value = 2 the  
thermostat goes to Heating mode, if the value = 3 the thermostat goes to Cooling Mode.  
The factory default value is 1.  
Parameters 42-45 – Schedule Time  
Use these parameters to manual set the Morning, Day, Evening and Night times for the Temperature Schedules.  
The value of these parameters has format HHMM, e.g. for 08:00 use value 0800 (time without a colon). From 00:00 to  
23:59 can be selected.  
The factory default value for Morning (Parameter 42) is 0600.  
The factory default value for Day (Parameter 43) is 0900.  
The factory default value for Evening (Parameter 44) is 1800.  
The factory default value for Night (Parameter 45) is 2300.  
Parameters 46-73 – Schedule Temperature  
Use these parameters to manual set the temperature for each day Schedule.  
The value of this parameter should be x10, e.g. for 22.5°C use value “225.” From 4°C to 37°C can be selected.  
Factory default parameters  
Default  
Value  
Available  
Values  
Number  
Size  
Name  
Description  
01  
02  
1 byte TIME CORRECTION  
1 byte TIME FORMAT  
Time correction by controller  
Time format  
1
0
0, 1  
0, 1  
1, 2, 3, 4, 5,  
6, 7  
03  
1 byte WEEKDAY  
Week Day  
1
04  
05  
06  
07  
08  
09  
10  
1 byte HOUR  
Time Hour  
0
0
0…23  
0…59  
1 byte MINUTE  
Time Minute  
1 byte DEGREE MODE  
1 byte AIR TEMP CORRECTION  
1 byte TEMP HYSTERESIS  
1 byte AUTO BRIGHTNESS  
1 byte MANUAL BRIGHTNESS  
Degree Mode  
0
0, 1(C_F)  
-95 … 95  
2…100  
0, 1  
Air Temperature Calibration in °C, x10  
Temperature Hysteresis in °C, x10  
Display auto-brightness control  
Display manual brightness level  
0
5
1
10  
1…15  
Touch buttons sensitivity.  
5 = Highly sensitive. 50 = Lowest  
sensitivity  
1 byte TOUCH THRESHOLD  
1 byte  
15  
2
5…50  
11  
12, 13  
Reserved by the manufacturer  
Mode to switch to when Basic Set  
command received  
0, 1, 2, 3, 4,  
5, 6, 7, 8, 9  
BASIC SET MODE  
1 byte  
14  
16  
GeneralDetails
NameHELTUN Fan Coil Thermostat HE-FT01 User Manual
MakeHELTUN
LanguageEnglish
FiletypePDF (Download)
File size0.35 MB
Download PDF