HELTUN Fan Coil Thermostat HE-FT01 User Manual
| General | Details |
|---|---|
| Name | HELTUN Fan Coil Thermostat HE-FT01 User Manual |
| Make | HELTUN |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.35 MB |


HELTUN HE-FT01 Manual: Questions and Answers
HELTUN HE-FT01 specifications
| Power supply | 85-265VAC 50Hz/60Hz, 24-48VDC |
| Display range | –30°C to +80°C |
| Operating temperature | 0° to +50° |
| IP rating | IP21 |
| Power consumption | 1W |
What does the 'tCr' setting mean on HELTUN HE-FT01?
Parameter 01 controls whether the thermostat automatically syncs its time and day with a Z-Wave gateway. Set to 1 for auto-correction, 0 to disable it. Factory default is 1. User Manual, p. 11
How do I change the time format to 12-hour on HELTUN HE-FT01?
Access Parameter 02 (tFo) in installer settings. Set the value to 1 for 12-hour AM/PM format, or 0 for 24-hour format. User Manual, p. 11
What's the difference between Parameter 09 and Parameter 10 on HELTUN HE-FT01?
| Parameter | Function |
|---|---|
| Parameter 09 (Abc) | Toggles automatic brightness control on/off; value 1 = auto, value 0 = manual |
| Parameter 10 (ldb) | Sets manual brightness level from 1 to 15 when Parameter 09 is set to manual mode |
How do I set up a temperature schedule?
Press and hold the Clock button for three seconds to enter the Time menu, where you can configure Set Points and times for Morning, Day, Evening, and Night schedules.
- Press and hold the Clock button for three seconds
- The display changes to the Time menu
- Set temperature and time for each schedule period User Manual, p. 8
At what temperature difference does HELTUN HE-FT01 switch fan speeds in Auto High mode?
Low speed runs when the difference is less than 1.0°C. Medium speed runs when the difference is 1.0°C or higher but less than 2.0°C. High speed runs when the difference is 2.0°C or higher. User Manual, p. 7
What is the temperature measurement range for HELTUN HE-FT01?
-30°C to +80°C. User Manual, p. 3
Can you tell if HELTUN HE-FT01 is connected to Z-Wave?
The display shows Z-Wave network status indicator. Check for the Z-Wave status symbol on the LCD screen. User Manual, p. 3
HELTUN HE-FT01 compared with other HELTUN thermostats
| Specification | HELTUN HE-FT01 | HELTUN HE-HT01 |
|---|---|---|
| Power supply | 85-265VAC 50Hz/60Hz, 24-48VDC | 85-265VAC 50Hz/60Hz or 24-48VDC |
| Display range | –30°C to +80°C | –30°C to +80°C |
| Operating temperature | 0° to +50° | 0° to +50° |
| IP rating | IP21 | IP21 |
| Power consumption | 1W | <1W |