HELTUN Fan Coil Thermostat HE-FT01 User Manual
Disassembly
1. To disassemble, ENSURE POWER IS SWITCHED OFF at the main circuit breaker AND THE LCD SCREEN IS
BLANK.
2. To remove the HE-FT01 display unit, grasp firmly at the bottom and pull backwards while tilting outwards until all
tabs disconnect.
3. Remove screws from backplate and disconnect the wires by inserting a small Phillips-head screwdriver into the slot
beneath each wire and turning counter-clockwise to release.
Touch Panel Operation
The touch panel has six capacitive-touch buttons which require minimal pressure to operate.
Symbol: Name:
Function:
Plus
Increase Set Point Temperature
Minus
Time
Decrease Set Point Temperature
Change Schedule
Climate
FAN Speed
Mode
Change Climate Modes and Open Parameters Menu
Change Fan speed
Change the Operational Mode: (COM, TIME, ECO, OFF)
The Plus “+” button will increase Set Point temperature by 0.5°C (1°F) with each touch. The Minus “–” button will
decrease Set Point temperature by the same 0.5°C (1°F). The Set Point temperature is displayed in the bottom left
corner of the LCD display under “SET TEMP.”
Note: The minimum Set Point is 4.0°C (39°F) and the maximum Set Point is 37.0°C (98°F).
The HE-FT01 has four operating states: 1) HEATING (OUT-4 is On, OUT-5 is Off), 2) COOLING (OUT-5 is On and
OUT-4 is Off), 3) VENTILATION (both OUT-4 and OUT-5 are Off) and 4) IDLE (all outputs are Off). In the HEATING
and COOLING states, in addition to OUT-4 & OUT-5, one output from OUT-1, OUT-2, & OUT-3 will be switched on
depending on selected speed. The icons HEATING, COOLING, & VENTILATION are displayed in the center, bottom
of the display. Those icons will disappear when the HE-FT01 is in IDLE mode.