Engineering Menu Items Table BAST-421C-BW2  
°C Scale  
°F Scale  
Step  
Item Mnemonic  
Description  
Default  
Range  
Default  
Range  
E1  
db  
Deadband  
2.0  
28  
0~10  
4.0  
0~18  
0.5 (°C/°F)  
1.0 (°C/°F)  
Unoccupied(ESI) cooling set point  
E2  
E3  
ESIC  
25~35  
82.5  
77~95  
Unoccupied(ESI) heating set point  
ESIH  
15  
10.0~22.0  
59  
50.0~72.0  
1.0 (°C/°F)  
10 (Sec.)  
Integral Time and Output Cycle Time  
(seconds)  
Minimum output voltage in digital value for  
AO1 when reach Low limit  
E4  
E5  
I-t  
60  
0~500  
0~125  
60  
0-500  
0~125  
0(0V)  
0(0V)  
OPL1  
1 (LSB)  
(0.044V)  
-20(10V)  
-20(10V)  
1 (LSB)  
(0.044V)  
E6  
SPA1  
AO1 Span Offset  
-55~0  
0~50  
0~50  
-55~0  
32~122  
32~122  
Low limit for temperature set point  
E7  
E8  
SP-L  
SP-H  
10  
30  
50  
95  
1.0 (°C/°F)  
1.0 (°C/°F)  
High limit for temperature set point  
E9  
OFSt  
Pb  
Current temperature offset  
Proportional band or stage width  
Stage differential  
0.0  
1.5  
0.5  
-10.0~10.0  
0~10.0  
0.0  
3.0  
1.0  
-18.0~18.0  
0~18.0  
0.1 (°C/°F)  
0.1 (°C/°F)  
0.1 (°C/°F)  
E10  
E11  
diFF  
0.1~1.0  
0.1~1.8  
Bit Definition:  
E12  
LOC  
0: MODE button (dec=1)  
1: Down buttons (dec=2)  
2: Up button (dec=4)  
3: FAN SPEED button (dec=8)  
4: Power On/Off button (dec=16)  
5: SET (or /) button (dec=32)  
6: ESI contact detection (dec=64)  
7: Door/Window contact detection  
(dec=128)  
8: Modification for communication  
parameters (dec=256)  
i.e. baud rate, MAC addr, device inst.  
9: Control DOs by thermostat algorithm  
(0) or BACnet sup. (1) (dec=512)  
10~15: reserved/unused  
64  
0-1023  
64  
0-1023  
1
Bit Value  
0: Unlock / enable  
1: Lock / disable  
Examples (add dec values to lock multiples)  
Unlock/enable all (0)  
Lock MODE Button (1)  
Lock Down Button (2)  
Lock MODE & Down Buttons (3 = 1+2)  
Lock Power On/Off button (4)  
Lock MODE & Power & Down (7 = 1+2+4)  
Lock SET button (32)  
Lock MODE & Down & Power & SET (39 =  
1+2+4+32)  
ESI contact disable (64)  
Lock the modification for communication  
parameters (256)  
DOs control commanded by BACnet (512)  
UM-15093000-AA2  
Page 18  
GeneralDetails
NameCONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual
MakeCONTEMPORARY CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual