** NOTE:  
1. Changing these values needs to unlock modification for communication parameters in advance. Please refer to the parameter  
LOC(Lock, AV17) for details.  
2. Device instance number = “devH” *1000 + “devL” = 0~4194302. ex. If “devH” is 100 and devL” is 001then the Device instance  
number = 100001.  
Lock Function Setup and Examples  
The 16-bit binary encoded decimal register accessed through Lock [AV17] BACnet object  
and LOC engineering menu item is used to enable/disable features in the thermostat. The  
first 10 bits are used (bit 0 ~ bit 9), bits 10~15 are reserved/unused. Bits are represented by  
their decimal values and are added or subtracted to toggle from “0” to “1”. Add a bit’s decimal  
value to toggle to “1” or subtract a bit’s decimal value to toggle to “0”. See table below.  
Bit Definition:  
Decimal Value to Write:  
Add decimal values to lock multiples. Bold decimal number is the  
example value to write to Lock object. Examples:  
0: MODE button  
1: DOWN button  
2: UP button  
3: FAN SPEED button  
4: POWER On/Off button  
5: SET (or /) button  
6: ESI contact detection  
7: Door/Window contact  
detection (unused)  
(dec=1)  
(dec=2)  
(dec=4)  
(dec=8)  
(dec=16)  
(dec=32)  
(dec=64)  
Unlock/enable all (0) – this will also enable ESI DI1 (add 64 to all  
values below to maintain default occupancy selection over  
BACnet).  
Lock MODE button (1) Lock DOWN button (2)  
Lock MODE & DOWN (3 = 1+2)  
Lock UP button (4)  
(unused)  
8: Modification for communication  
Lock MODE & DOWN & UP (7 = 1+2+4)  
Lock FAN SPEED button (8)  
parameters  
i.e., baud rate, MAC addr, device inst.  
9: Control DOs by thermostat algorithm  
(dec=256)  
(0) or BACnet sup. (1)  
10~15: reserved/unused  
(dec=512)  
(unused)  
Lock MODE & DOWN & UP & FAN (15 = 1+2+4+8)  
Lock POWER button (16)  
Bit Value:  
Lock MODE & DOWN & UP & FAN & POWER (31 = 1+2+4+8+16)  
Lock SET button (32)  
0: Unlock / enable  
1: Lock / disable  
Lock MODE & DOWN & UP & FAN & POWER & SET (63 =  
1+2+4+8+16+32)  
ESI contact disable (64 – default). When the default value of 64 is  
maintained, occupancy is set over BACnet and SET user button.  
Lock MODE & DOWN & UP & FAN & POWER & SET & disable  
ESI DI1 (127 = 1+2+4+8+16+32+64)  
Door/Window contact detection (unused)  
Lock the modification for communication parameters such as baud  
rate and mac address (256)  
Lock MODE & DOWN & UP & FAN & POWER & SET & disable  
ESI DI1 & modification for communication parameters (383 =  
1+2+4+8+16+32+64+256)  
DOs control commanded by BACnet (512)  
Page 21  
UM-15093000-AA2  
GeneralDetails
NameCONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual
MakeCONTEMPORARY CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual