Readable/  
Writable  
Object name  
Description  
Range and Definition  
Unoccupied Heat  
Setpoint  
Unoccupied Heating  
Setpoint  
°C: 100~220 (10.0~22.0°C)  
°F: 500~715(50.0~71.5°F)  
AV 9  
R/W  
AV 10  
R/W  
Integral-Cycle Time  
Integral Time and Output  
Cycle Time  
0~500 (Sec.)  
AV 11  
AV 12  
AV 13  
AV 14  
AV 15  
AV 16  
AV 17  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
R/W  
Analog Minimum  
Output for AO1  
Minimum Output Voltage  
in Digital Value When  
Reach Low Limit for AO1  
0~125 (LSB)  
-55~0 (LSB)  
Span Offset for AO1  
Span Offset for AO1  
°C :0~500 (0.050.0)  
Low Setpoint Limit  
High Setpoint Limit  
Temperature Offset  
Low Limit for Set-Point  
Temperature  
°F: 320~1220(32.0~122.0°F)  
°C :0~500 (0.050.0)  
High Limit for Set-Point  
Temperature  
°F: 320~1220(32.0~122.0°F)  
°C: -100~100 (- 10.0~10.0°C)  
°F: -180~180 (-18.0~18.0°F)  
Offset for Current  
Temperature  
°C :0~100 (00~10.0 °C)  
°F: 0~180 (00~18.0 °F)  
Proportional Band-  
Stage Width  
Proportional Band or Stage  
Width  
°C :1~10 (0.1~1.0 °C)  
°F: 1~18 (0.1~1.8 °F)  
Stage Differential  
Stage Differential  
Page 24  
UM-15093000-AA2  
GeneralDetails
NameCONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual
MakeCONTEMPORARY CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual