Home > CONTEMPORARY CONTROLS > CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual

CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual

Type &  
Instance  
Readable/  
Writable  
Object name  
Description  
Range and Definition  
Maximum Fan  
Output  
Maximum Fan Output at  
Auto Fan Mode (for  
Modulating Fan Application)  
Low Fan Speed  
R/W  
R/W  
AV 42  
AV 43  
Reg 50~100%  
0%~Reg 53  
Low Fan Speed  
Setting  
Setting (for  
Modulating Fan  
Med. Fan Speed  
Setting  
Med. Fan Speed Setting (for  
Modulating Fan  
Application)  
Hi Fan Speed  
Setting (For  
AV 44  
AV 45  
R/W  
R/W  
Reg 52~Reg54  
Reg 53~100%  
Hi Fan Speed  
Setting  
Modulating Fan  
Minimum Off  
Time  
AV 46  
AV 47  
AV 48  
R/W  
R/W  
R/W  
Minimum Off Time  
Minimum On Time  
0~600 seconds  
Minimum On  
Time  
0~600 seconds  
0~500 (Sec.)  
Integral-Cycle  
Time 2  
Integral Time and Output  
Cycle Time 2  
Set Point for  
Humidity  
Set Point for  
Humidity Control  
0~1000 (0.0100.0%RH)  
AV 49  
AV 50  
R/W  
R/W  
Dew Point Set  
Point  
Dew Point  
Temperature Set  
Point  
-999~9999: -99.9999.9  
/°F  
Occupancy  
Status  
Status of  
Occupancy  
BI 0  
BI 1  
BI 2  
R
R
R
0: Room Occupied  
1: Room Unoccupied  
Window-Door  
Status  
Window/ Door  
Status  
0: Door/Window Closed  
1: Door/Window Open  
Cooling-heating  
Status  
Status of Cooling/Heating  
Control Output  
0: Close & Off 1: Open & On  
Status of Relay 1  
BI 3  
BI 4  
R
R
Relay 1 Status  
Relay 2 Status  
0: Off, 1: On  
0: Off, 1: On  
Status of Relay 2  
Status of Relay 3  
Status of Relay 4  
BI 5  
BI 6  
R
R
Relay 3 Status  
Relay 4 Status  
0: Off, 1: On  
0: Off, 1: On  
Status of Relay 5  
Status of Relay 6  
BI 7  
BI 8  
R
R
Relay 5 Status  
Relay 6 Status  
0: Off, 1: On  
0: Off, 1: On  
Status of Relay 7 Fan  
Status of Digital Input 1  
BI 9  
R
R
Relay 7 Status  
Dl 1 Status  
0: Off, 1: On  
0: Off, 1: On  
BI 10  
Status of Digital Input 2  
BI 11  
R
Dl 2 Status  
0: Off, 1: On  
Page 27  
UM-15093000-AA2  
GeneralDetails
NameCONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual
MakeCONTEMPORARY CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual