Floating Deadband  
The Heat and Cool temperature setpoints could be “attached” together. This  
means that as one setpoint is adjusted and “hits” against the deadband  
region, it will “push” the deadband region and the other setpoint along the  
temperature setpoint axis to allow for adjustment while maintaining the  
configured deadband. If the setpoint is adjusted back the other way, it will  
“pull” the deadband region and the other setpoint along the temperature  
setpoint axis.  
Minimum Cooling Setpoint and Maximum Heating Setpoint  
Minimum Cooling Setpoint will be confined by set point low limit plus  
dead band and Minimum cooling setpoint [AV-39] Default 18°C/ 65°F  
Maximum Heating Setpoint will be confined by set point high limit  
minus dead band and Maximum heating setpoint [AV-40] Default  
25°C/ 77°F  
Fan Control Output  
Lowest Fan Speed is the speed the fan will default to after a control action  
(Heating or Cooling) with fan in AUTO mode. If the lowest fan speed  
[MSV4] is set as “Stop (1)”, the fan will automatically shut off after the  
control action plus a 2-minute fan-off time delay. During this delay, the AUTO  
icon will flash. If lowest fan speed is set to “Low (2)” the fan will run  
continuously after a control action  
Fan Mode can be toggled between AUTO or ON by using the FAN button on the  
thermostat or BACnet object [MSV0] Fan Mode (BACnet supervisor). By default,  
this value is set to “Auto(1)”, the AUTO icon is displayed, and fan operation will  
be controlled automatically. To put the fan in ON mode set [MSV0] to “Low(2)”.  
This will cause the fan to run continuously (no AUTO icon is displayed). Fan  
icon spins when fan is active. The FAN button can be locked to limit user  
access to this feature or the BACnet supervisor can be programmed to default  
the thermostat to certain state at the end of an occupancy cycle.  
UM-15093000-AA2  
Page 15  
GeneralDetails
NameCONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual
MakeCONTEMPORARY CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual