2 Specifications  
2.1 Inputs  
Item  
Description  
Temperature Display Range  
-22 to 248 °F (-30 to 120.0°C) with suitable sensor  
Temperature Display Resolution 0.1°F (0.1°C)  
Temperature Accuracy  
Energy Savings Input  
Setpoint Range  
±1.8°F (±1.0°C) with all outputs off  
Provision for external occupancy sensor  
32-122°F (0-50°C) in 0.5° (°F or °C) increments  
Provision for NTC Type 3kΩ thermistor  
Remote Temperature Sensor  
2.2 Outputs  
Item  
Relay Output  
Description  
Fan  
Analog Outputs  
Contact Rating  
0-10v modulating AO1 (cooling), AO2 (heating)  
SPST 2A at 30 VAC with inductive load  
100,000 cycles  
Minimum contact life  
2.3 Communication  
Item  
Protocol Compliance  
Physical Layer  
Baud Rate  
Description  
BACnet/MSTP with B-ASC, BTL Listed  
RS-485 2-wire  
9.6, 19.2, 38.4, 76.8 kbps (default 38.4kbps) N81 format  
Shielded single-pair twisted 24 GA AWG  
Cabling  
2.4 Electrical  
Item  
Description  
24 VAC (±10%) 5 VA  
Supply Voltage and Current  
Power Source Class  
Internal Power Supply  
NFPA 70 (NEC) Article 725 Part III Class 2  
Half-wave rectified and filtered DC  
UM-15093000-AA2  
Page 6  
GeneralDetails
NameCONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual
MakeCONTEMPORARY CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

CONTEMPORARY CONTROLS BAST-421C-B2 BACnet Communicating Thermostat User Manual