Home > Blue Universal > Blue Universal OH-1202 Touchscreen Thermostat Instruction Manual

Blue Universal OH-1202 Touchscreen Thermostat Instruction Manual

INSTALLER/CONFIGURATION MENU  
To enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Config touch key. This displays  
screen reference #1 in the table below. Screen Reference numbers appear in top right corner of display. Press  
to the next menu item or to return to a previous menu item. Press or to change a menu item option. Shaded items are  
not available if selected for Non-Programmable. Write the options selected in the "Option Selected" column of the menu.  
to advance  
Installer Note: To default the programming, clock and Configuration Menu to the Factory Default Settings, press the  
and SYSTEM keys simultaneously. The thermostat display will go blank for a few seconds, and then all segments will display  
momentarily. For heat pump systems, Configuration Menu items 1 and 3 must be set to match the heat pump system.  
,
CONFIGURATION MENU  
Screen  
Reference  
Number  
Displayed  
Factory  
(Default)  
Press  
or  
Press  
key  
SS1 HP1  
MS2 HP2  
Option  
Selected  
Comments  
to select from  
listed options  
HP 1, HP 2, SS 1  
1
MS 2  
Selects Multi-Stage (MS2, No Heat Pump), Heat Pump 1  
(HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor  
or 2 speed compressor), or Single Stage.  
2
3
(GAS)  
0b (0)  
ELE  
b
GAS setting: furnace controls blower.  
ELE setting: thermostat controls blower.  
Selects Reversing Valve (This item is only to appear if HP1 or HP2  
is selected above.)  
4
5
Days, (7) P  
5 or 0  
Programs per week. (7 days, 5+1+1 days or non-programmable)  
(4) PS  
2
Programs per day.  
4 = Morning, Day, Evening, Night  
2 = Day, Night  
Not available if 4 is 0  
6
Cool-Off-  
Heat-Auto  
Cool-Off-Heat, Heat Off, System switch configuration in non heat pump mode.  
Heat, Cool-Off, Auto Off  
Cool-Off-Heat-  
Em-Auto  
Cool-Off-Heat-Em,  
Off-Em-Auto  
System switch configuration, heat pump mode.  
7
8
(On) E  
OFF  
SL  
Selects Energy Management Recovery. Not available if 4 is 0  
Selects Adjustable Anticipation, cycle rate, Heat  
Selects Adjustable Anticipation, cycle rate, Cool  
(FA) Heat, Cr  
(FA) Cool, Cr  
(FA) Cr/AU, Em  
9
SL  
10  
SL  
Selects Adjustable Anticipation, cycle rate auxiliary, (This item is  
only to appear if HP1 or HP2 is selected above).  
11  
12  
13  
14  
(OFF) SC  
(OFF) CL  
(OFF) dL  
On  
On  
Select stage cycle completion On or Off.  
Selects Compressor Lockout.  
On  
Selects Continuous Display backlight.  
0
(Temperature)  
5, LO to 5, HI  
Selects Adjustable Ambient Temperature Display [range -5 (LO) to  
+5 (HI)].  
15  
16  
17  
18  
°F  
°C  
Selects °F/°C Display (temperature units in Fahrenheit or Celsius).  
(On) b  
OFF  
OFF  
OFF  
Selects audible Beeper On/Off.  
(On) dS  
Selects Daylight Saving Time calculation.  
(On) Heat, AS  
Selects Automatic Schedule for comfort temperature Programming,  
heat mode. Not available if 4 is 0  
19  
(On) Cool, AS  
OFF  
Selects Automatic Schedule for comfort temperature Programming,  
cool mode. Not available if 4 is 0  
20  
21  
(OFF) CS  
On  
Selects Cool Savings Feature On of Off.  
CS Cool Savings  
(3)  
1-2-3-4-5-6  
Selects amount of Cool Savings adjustment.  
22  
23  
(Off) CO  
On  
On  
Select Compressor Optimization (not available on earlier models)  
(OFF) CA  
Selects Comfort Alert Feature On or Off. (not available on earlier  
models)  
24  
25  
26  
(99) Heat, HL  
62-98  
46-82  
TEMPERATURE LIMIT, HEAT (max. heat set point).  
TEMPERATURE LIMIT, COOL (min. cool set point).  
Selects Keypad Lockout.  
(45) Cool, LL  
L (total), P (partial),  
Temperature Limit  
(limited temperature range)  
OFF,  
Keypad Lockout  
27  
000  
001-999  
Selects Keypad Lockout Combination (active only if keypad Lockout  
is selected).  
28  
29  
(On) Heat, FS  
(On) Cool, FS  
OFF  
OFF  
Fast second stage of heat (not available if SS1 is selected above).  
Fast second stage of cool (not available if SS1 or HP1 is selected  
above).  
30  
31  
Remote (OFF)  
Remote, In  
On  
Remote temperature sensor, enable/disable.  
Outdoor Remote  
Remote temperature sensor (Indoor/Outdoor).  
32  
(On) LS  
OFF  
Local temp. Sensor enable/disable (only when Indoor Remote is  
selected On).  
5