point is 22°C (72°F) and you set the heating setpoint to 23°C (73°F),
the cooling setpoint will automatically become 24°C (75°F). How-
ever, if you raise the heating setpoint to 21°C (70°F), the cooling
setpoint will remain at 22°C (72°F). The same principle applies
when you set the cooling temperature.
Temperature Adjustment
6.3
6.3.1 Manual Adjustment
Use this mode to set the temperature manually. To place the con-
troller in this mode, press Auto/Man so that disappears from the
•
Press
to exit.
screen. Set the temperature using the
buttons.
The following diagram shows how to navigate the programming
menu.
NOTE: If the controller is in automatic heat/cool changeover (see
section 6.2), the setpoint is automatically reduced or raised by 1°C
(1.8°F) when the controller switches to heating mode or to cooling
mode respectively. For example, if the setpoint is 24°C (75°F) in
heating mode, it will become 25°C (77°F) in cooling mode and will
return to 24°C (75°F) when the controller switches back to heating
mode.
MO
TU
6:00
6:00
Day
Pgm
Pgm
6.3.2 Automatic Adjustment
P1
Use this mode if you want the controller to adjust the temperature
according to the programmed schedule. To place the controller in
this mode, press Auto/Man so that appears on the screen.
Cool
Cool
Heat
Heat
Mode
Mode
21
25.5
21
25.5
Pre-programmed Schedule
Pgm
Pgm
The following schedule has been programmed at the factory. Two
temperature settings are programmed for each period of the sched-
ule: a heating setpoint and a cooling setpoint.
8:00
8:00
Pre-programmed Schedule
MO TU WE TH FR SA SU
Pgm
Day
Pgm
P2
Heating
21°C (70°F)
6:00 a.m.
Cool
Cool
Heat
Heat
P1
P2
P3
P4
Mode
Cooling 25.5°C (78°F)
Heating 16.5°C (62°F)
Cooling 29.5°C (85°F)
Mode
16.5
29.5
16.5
29.5
8:00 a.m.
6:00 p.m.
--
--
Temporary Bypass
Heating
21°C (70°F)
When you modify the temperature setpoint while the controller is in
automatic mode, the new temperature is used for the next 2 hours.
The icon flashes during the bypass. After the bypass, the temper-
ature set for the current period is used.
Cooling 25.5°C (78°F)
Heating 16.5°C (62°F)
10:00 p.m.
Cooling
28°C (82°F)
Modifying the Schedule
Unoccupied Mode
6.4
You can program up to 4 periods per day. To program a period, you
need to set the start time, the heating setpoint and the cooling set-
point. The program can be different for each day of the week.
You can place the controller in the unoccupied mode using a remote
control device such as Aube’s CT241 telephone controller. In this
mode, the temperature is lowered in heating mode or raised in cool-
ing mode (see page 8, item 16). The message UNOC appears during
the unoccupied mode.
•
Press Pgm to enter the programming mode. The settings for
Monday, Period 1 (P1) appear.
•
To select a day to program, press Day until the day is dis-
played. Press for 3 seconds to select all 7 days.
NOTE: Automatic changeover is disabled during the unoccupied
mode.
NOTE: If you select all 7 days, the settings of the displayed
period will be copied to all 7 days. For example, if you select all
7 days while period 1 is displayed, they will all now have the
same settings for period 1. If you display period 2 while all 7
days are selected, they will all now have the same settings for
period 2.
Temporary Bypass
In the unoccupied mode, only the
buttons work. When you
adjust the temperature during this mode, the new temperature will
be used for the next 2 hours, after which the controller will return to
the previous setpoint. The message UNOC flashes during the bypass.
•
To set the start time of a period, press Pgm until the period
number (P1 to P4) is displayed and the time display flashes.
Then press the
15 minutes.
buttons. The time changes in increments of
NOTE: To skip a period, display the period and press Clr. For
example, in the pre-programmed schedule, periods 2 and 3
have been skipped for Saturday and Sunday.
•
To set the temperatures for a period, press Pgm until the period
number (P1 to P4) is displayed and the temperature display
flashes. If necessary, press Mode to display the heating set-
point or the cooling setpoint. Press the
temperature.
buttons to set the
NOTE: The cooling setpoint is always higher than the heating set-
point by a minimum of 1°C (1.8°F). For example, if the cooling set-
TH146-P-2H1C
400-280-014-A
5/23/07
10/11