4.4 Types of Heat Pump Installations  
4. Principles of Operation  
4.1 Automatic Heating/Cooling Changeover  
The controller can be configured for either of the following types of  
heat pump installations (see page 8, item 8).  
Add-on Installation: This type of installation is performed  
when adding a heat pump to an existing furnace. When the  
heat pump is installed, the furnace becomes the auxiliary heat  
source. In this type of installation, the indoor coils are usually  
installed downstream of the auxiliary heat source. When the  
controller is configured for an add-on installation, the heat  
pump is disabled during auxiliary heating to prevent overpres-  
sure.  
With automatic heating/cooling mode changeover, there’s no need  
to adjust the controller at every change of season or weather condi-  
tion. The controller switches automatically between heating mode  
and cooling mode to maintain the desired temperature.  
Manual Mode  
When the controller is in manual mode, the heating/cooling mode  
changeover occurs as follows:  
New Installation: In this type of installation, as there is not  
already a furnace, the auxiliary heat source is installed at the  
same time as the heat pump. In this type of installation, the  
indoor coils are located upstream of the auxiliary heat. When  
the controller is configured for a new installation, the heat pump  
and the auxiliary heat can operate simultaneously.  
The controller switches to cooling mode when the indoor tem-  
perature is higher than the setpoint by more than 1.5°C (2.5°F)  
for 15 minutes.  
The controller switches the heating mode when the indoor tem-  
perature is lower than the setpoint by more than 1.5°C (2.5°F)  
for 15 minutes.  
4.5 Interstage Delay  
Automatic Mode  
When the controller is in automatic mode, it follows the programmed  
schedule. Two temperature settings (heating setpoint and cooling  
setpoint) are programmed for each period of the schedule. The  
heating/cooling mode changeover occurs as follows:  
Interstage Delay is the time allocated for the temperature to return  
to an acceptable value when it deviates too far from the setpoint. If  
this time has elapsed, the next heating or cooling stage is activated.  
The heating or cooling stage will be deactivated when the tempera-  
ture returns to an acceptable value. The Interstage Delay is fixed at  
4 minutes if the controller is configured for an HVAC system and is  
user-adjustable if it is configured for a heat pump (see page 8,  
item 9).  
When the controller is in heating mode, the indoor temperature  
is maintained at the heating setpoint. However, if the tempera-  
ture rises and remains above the cooling setpoint for 15 min-  
utes, the controller will switch to cooling mode.  
When the controller is in cooling mode, the indoor temperature  
is maintained at the cooling setpoint. However, if the tempera-  
ture drops and remains below the heating setpoint for 15 min-  
utes, the controller will switch to heating mode.  
4.6 Low and High Temperature Limits  
Low Temperature Limit (LLMT) and High Temperature Limit (HLMT)  
are used to keep the plenum from becoming too cold or too hot.  
During cooling, if the plenum temperature is lower than LLMT, a  
cooling stage is deactivated starting with the one that was last acti-  
vated. If, after a while, the temperature is still too low, another cool-  
ing stage is deactivated and so on. Likewise, during heating, if the  
plenum temperature is higher than HLMT, a heating stage is deacti-  
vated starting with the one that was last activated. If, after a while,  
the temperature is still too high, another heating stage is deacti-  
vated and so on. (see page 8, items 10 and 11.)  
4.2 Balance Points (heat pumps only)  
Balance Points are used to disable the heat pump or the auxiliary  
heating when the outdoor temperature is below or above a set tem-  
perature.  
When the outdoor temperature is below the Balance Point Low  
(bP L), the heat pump is disabled and only auxiliary heating can  
be used (see page 8, item 5).  
WARNING: LLMT and HLMT can be used in parallel with an  
UL353-approved device but they do not replace such device.  
NOTE: LLMT and HLMT cannot be used if the plenum temperature  
sensor is not connected to the controller.  
When the outdoor temperature is above the Balance Point High  
(bP H), the auxiliary heat is disabled and only the heat pump  
can be used (see page 8, item 6).  
NOTE: Balance Points cannot be used if the AC144-03 outdoor  
temperature sensor is not connected to the controller.  
4.7 Smart Fan  
4.3 Heating During Defrost (heat pumps only)  
When Smart Fan is enabled (see page 8, item 15), the fan operates  
as follows:  
The auxiliary heat is activated during defrost except under the fol-  
lowing conditions:  
During periods 2 and 4 of automatic mode and during the unoc-  
cupied mode (i.e., when you are away from home or sleeping),  
the fan operates only when heating or cooling is activated.  
The fan operates continuously the rest of the time.  
When the outdoor temperature is above the defrost point (see  
page 8, item 7). Note: This condition will not apply if the  
AC144-03 outdoor sensor is not connected to the controller.  
NOTE: For Smart Fan to work, set the fan to On (see section 5.3).  
When the plenum temperature is above 40°C (104°F). The  
auxiliary heat is re-activated when the plenum temperature  
drops below 32°C (90°F). Note: This condition will not apply if  
the AC146-410 plenum sensor is not connected to the control-  
ler.  
NOTE: The auxiliary heat’s short-cycle protection is disabled during  
defrost.  
TH146-P-2H1C  
400-280-014-A  
5/23/07  
3/11  
GeneralDetails
Nameaube TH146-P-2H1C Programmable Thermostat Installation Guide
Makeaube
LanguageEnglish
FiletypePDF (Download)
File size0.46 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
aube Electronic Thermostat TH131 Owner’s Manual
aube Electronic Thermostat TH131 Owner’s Manual
aube TH114-AF-GA Non-Programmable Thermostat Owner’s Manual
aube TH114-AF-GA Non-Programmable Thermostat Owner’s Manual

aube TH146-P-2H1C Programmable Thermostat Installation Guide