Home > EAE Technology > EAE Technology EAE-KNX MONA Series Thermostat Instruction Manual

EAE Technology EAE-KNX MONA Series Thermostat Instruction Manual

Installation Manual MONA Series  
EAE KNX MONA Thermostat  
MONA Thermostat R0  
Device Descrip�on  
Installa�on  
MONA premium thermostat  
series create a natural harmony  
and adds value to your interior  
designs with elegant look and  
sophis�cated technology. It is  
used to control the HVAC systems  
including control the switches,  
dim the lights, ac�va�ng scenes,  
control blinds and vice versa.  
Installa�on of the product is done with metal flange. It is fixed to the  
junc�on box by using screws. The switch has magnets and should be  
posi�oned the screen upwards. The device will s�ck on flange via  
magne�za�on. Mul�ple devices can be combined up to 3.  
NOTE: Distance between center of flanges is 71 mm.  
•
•
•
•
•
Monoblock glass design  
60x60 mm easy moun�ng to standard junc�on boxes.  
Different glass color op�ons  
Configurable RGB illuminated bu�ons  
Up to 6 independent programmable bu�ons  
. Switching  
. Dimming  
. Shu�er/Blind  
. Value  
. Scene control  
. Status no�fica�on  
Opera�on and Display  
7
8
5
6
9
1
4
1. KNX Port Terminal  
2. Programming LED  
3. Programming Bu�on  
4. Control Bu�ons  
6. Opera�on Mode Bu�on  
(Comfort, Night, Away, Protec�on)  
7. Setpoint Temperature UP  
8. Setpoint Temperature DOWN  
9. Built-in Screen  
Commissioning  
Device default physical address is 15.15.255. Determina�on of the  
physical address and se�ng of parameters are actualized with  
Engineering Tool So�ware (ETS4 or higher). “.knxprod” file must be  
imported to the ETS. (h�p://www.eaetechnology.com/)  
5. Fan Speed (1, 2, 3, Auto)  
Technical Data  
Protec�on Type IP20  
II  
EN 60 529  
EN 61 140  
Bus Connec�on  
21V… 30V DC, KNX  
<21mA  
Addr Prog.LED  
Bu�on Status LEDs  
-5° C + 45° C  
-25° C + 55° C  
±0,3 °C  
A detailed informa�on about parameter configura�on can be  
found in Product Manual of device.  
Safety Class  
Connec�ons  
KNX  
Voltage  
Installa�on and commissioning of device may only be  
implemented by trained electricians. The relevant standards,  
direc�ves, regula�ons and instruc�ons must be observed when  
planning and implemen�ng the electrical installa�on.  
Power Supply  
Current drawn from bus  
LED (red)  
LED (white)  
Opera�ng  
Elements  
Opera�ng  
Temperature  
Temp. Sensor  
Ambient  
Storage  
Measurement Accuracy  
-Protect the device against moisture, dirt and damage during  
transport, storage and opera�on!  
Humidity  
Max. Air humidity  
Front side  
95% no moisture  
90 x 100 mm  
12 mm  
-Do not operate the device out of the specified technical data which is  
stated.  
Dimensions  
Side – Surface mounted part  
Side – Flush mounted part  
65 g  
18.8 mm  
Weight  
-The device may only be operated in closed enclosures (Distribu�on  
boards)  
Glass – Surface  
Polycarbonate – Flush mounted part  
Front Side – Glass – Black or White  
Flush mounted part – Polycarbonate - Black  
In accordance with the EMC guideline and low voltage  
direc�ves  
Box Material  
Color  
CE  
Cleaning  
If device becomes dirty, only a dry cloth can be used for cleaning. İt is  
not suitable to use wet cloths, caus�cs and solvents.  
© EAE Technology  
GeneralDetails
NameEAE Technology EAE-KNX MONA Series Thermostat Instruction Manual
MakeEAE Technology
LanguageEnglish
FiletypePDF (Download)
File size0.23 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
EAE TECHNOLOGY KNX ORIA Thermostat Installation Guide
EAE TECHNOLOGY KNX ORIA Thermostat Installation Guide

EAE Technology EAE-KNX MONA Series Thermostat Instruction Manual
Get the free PDF manual for the EAE Technology EAE-KNX MONA Series Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

EAE Technology EAE-KNX MONA Manual: Questions and Answers

EAE Technology EAE-KNX MONA specifications

Accuracy±0,3 °C
Operating temperature-5° C + 45° C
Storage temperature-25° C + 55° C
Weight65 g

Full specifications, page 1

Where are the programming button and LED located on this thermostat?

The programming LED is at position 2 and the programming button at position 3 on the front face. Instruction Manual, p. 1

What is the voltage requirement for EAE Technology EAE-KNX MONA?

21V to 30V DC, with current drawn from the KNX bus under 21mA. Instruction Manual, p. 1

Can I mount multiple EAE Technology EAE-KNX MONA units side by side in the same junction box?

Yes, up to 3 devices can be combined. The distance between the center of flanges must be 71 mm. Instruction Manual, p. 1

How do I install EAE Technology EAE-KNX MONA to a standard junction box?

Use the metal flange with screws. Position the screen upwards. The device attaches to the flange via magnetization.

  1. Fix the metal flange to the junction box with screws.
  2. Orient the screen to face upward.
  3. The device will stick to the flange magnetically. Instruction Manual, p. 1

More EAE Technology thermostat manuals