Unisenza 230V-24V Stats Wired and Wireless Thermostat User Manual
Unisenza PLUS - UFH Thermostat 230V/24V
Installation and user manual
EN
2
TECHNICAL DATA
UFH Thermostat 230V/24V
Temperature Scale
°C or °F
Temperature Display Range
Temperature Display Resolution
Temperature Setting Range
Temperature Setting Resolution
Temperature Measurement Accuracy
Humidity Display Resolution
Humidity Measurement Accuracy
Firmware update
5 °C - 45 °C
0.1 °C o 0.5 °C
5 °C - 40 °C
0.5 °C
+/- 0.5 °C
1% RH
+/-5% @20%-80%RH, +/-8% @other range
Over the air firmware update capability
ZigBee 3.0, 2.4GHz
Wireless Communication
Relay switching rating
3A resistive, 1A inductive
230Vac +/-10% 50Hz
24Vac +/- 20% 50Hz
Power Supply
Operating Environment
Operating Temperature
Storage Temperature
Operating/Storage Humidity
Dimensions
Indoor, residential & commercial
0°C – 50 °C
-20 °C – 60°C
5-95% RH, non-condensing
86(W) x 86(D) x 27(H) mm
IP30
Ingress Protection Rating
Regulation
CE, UKCA
Environmental Requirement
RoHS compliance
The UFH Thermostat 230V/24V complies with the following European directives:
•
•
•
RED directive 2014/53/EU
ROHS directive 2011/65/EU
REACH (EC 1907/2006)
The UFH Thermostat 230V/24V complies with the relevant UK Statutory Instruments:
•
•
Electrical Equipment (Safety) Regulations 2016
Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment
Regulations 2012 (SI 2012/3032)
•
REACH ETC. (Amendment etc.) Regulations 2020 - SVHC