»INPUTS  
Up to 2 inputs are configurable for functions such as windows contact, dew point, occupancy, change-over or external sensor option.  
The overview of possible combinations can be found in the software specification of the JOY.  
Sensor (NTC10K) The value of an external sensor will be shown if connected and configured accordingly. In this case, the room thermostat  
controls according to the external sensor. Alternatively, an external temperature sensor can be used at the universal input  
to protect floor heating. If a configured temperature is exceeded, the heating sequence is suspended.  
Change-Over DI  
Which controller is active depends on the state of the Change-Over contact. (Factory default: contact open heating controller  
active, contact closed cooling controller active). The terminals 4 and 5 are used as outputs for heating rsp. cooling.  
Change-Over  
Sensor  
The Change-Over Sensor is used for switching between heating and cooling mode automatically. If the temperature is below  
22 ° C, the controller is in cooling mode. If it is above 25 ° C, it is a heating mode.  
If an input is configured as a change-over, the room thermostat is automatically in 2-pipe operating mode and both outputs  
(terminals 4 and 5) are used as outputs for heating rsp. cooling.  
Window  
If a window contact is enabled via the digital input, the reference will switch to a setback set point (Heat SP/Cool SP).  
contact/Energy  
hold off  
Dewpoint  
An active dewpoint contact locks the cooling controller.  
Occupancy  
If occupancy-function is active, the symbol will be displayed automatically. In state of “unoccupied” the heating set point is  
reduced by 2K (default setting) rsp. the cooling set point raised by 2K.  
Keycard-Switch  
Alarm contact  
When the card is not inserted, the device is switched in sleep mode. Operation of the keys is locked, the display is switched  
off and the controller adjusts to the nominal values of the "unoccupied"-State.  
An alarm symbol can be shown in the header of the display. The backlight flashes when the alarm is active. This symbol is  
in the same position as the ECO symbol. The alarm symbol has a higher priority and overwrites the ECO symbol!  
»DIMENSIONS (MM)  
»ACCESSORIES (OPTIONAL)  
Frame for surface mounting JOY pure white  
Frame for surface mounting JOY black  
Decorative frame pure white for JOY  
Decorative frame black for JOY  
MicroSD card 2GB  
Item No. 760201  
Item No. 760951  
Item No. 681452  
Item No. 740951  
Item No. 500098  
RS485 Biasing Adapter  
USB RS485 Modbus RTU Logger  
Converter RS485 Modbus - USB  
Item No. 811378  
Item No. 809917  
Item No. 668293  
JOY_SR Fancoil_Modbus_Datasheet_en © 2023  
GeneralDetails
Namethermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide
Makethermokon
LanguageEnglish
FiletypePDF (Download)
File size0.59 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
thermokon JOY 5DO Digital Room Thermostat User Manual
thermokon JOY 5DO Digital Room Thermostat User Manual

thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide