What's the difference between the JOY Fancoil 5DO and JOY Fancoil EC AO2DO?
The EC AO2DO has 2 relays and 1 analogue 0-10V output for EC fans, heating valve, cooling valve. The 5DO is for two-wire electric valves.
| JOY Fancoil 5DO | JOY Fancoil EC AO2DO |
|---|---|
| Two-wire electric valves | EC fans with 2 relays and 1 analogue 0-10V output |
| Two-pipe and four-pipe systems | 2-pipe and 4-pipe systems |
Can I use NTFS or exFAT filesystems on the MicroSD card for the Thermokon JOY?
No. Only FAT-filesystem is supported. NTFS and exFAT filesystems are not supported. User Manual, p. 2
How do I update the software on the Thermokon JOY 5DO?
Remove the upper part and insert a MicroSD card with a valid update file. Mount the upper part back. The update process starts automatically when the device recognizes the file.
- Remove upper part of the device
- Insert MicroSD card with valid update file
- Mount upper part back
- Wait for ring illumination to blink in 300ms cycle, indicating update is running
- Device restarts with new application after 20-30 seconds
- Remove upper part to take out the MicroSD card User Manual, p. 2
What do the blinking patterns of the ring illumination on the Thermokon JOY 5DO indicate?
A 1 second cycle means the bootloader is active. A 300ms cycle means an update is in progress.
| Blinking Pattern | Meaning |
|---|---|
| 1 second cycle | Active bootloader, display not responding |
| 300ms cycle | Update process running |
What does the occupancy symbol mean on Thermokon JOY display?
The occupancy symbol appears when the occupancy function is active. In unoccupied state, heating setpoint drops 2K and cooling setpoint rises 2K from their normal values. User Manual, p. 6
How long does the Thermokon JOY 5DO parameter menu stay open without interaction?
The parameter menu closes automatically after 8 minutes of inactivity. User Manual, p. 5
What temperature threshold triggers cooling mode on the Thermokon JOY 5DO?
Below 22°C the controller enters cooling mode. Above 25°C it switches to heating mode when using change-over sensor. User Manual, p. 6