Home > thermokon > thermokon JOY 5DO Digital Room Thermostat User Manual

thermokon JOY 5DO Digital Room Thermostat User Manual

Issue date: 22.06.2023  
Page 7 / 8  
»MENU → COMMON SETTINGS  
Common device settings:  
Brightness  
Valve protection  
Valve protection  
A valve protection function actuates the heating and cooling valves  
regularly to prevent locking during non-usage times.  
ECO deadband  
Fanstages (5DO only)  
Language  
The function is executed fridays at 11.00 (heating valve) and 11.15  
(cooling valve). The corresponding valve is triggered for 5 minutes, if not  
activated during the last 96 hours.  
Factory setting (reset)  
ECO deadband  
Brightness  
The dead band can be adjusted (default 10.0 K)  
* further information in the software specification file  
Configuration of the LCD brightness/ LED ring brightness during button  
operation/ usage.  
Factory setting  
By selecting “Factory setting”, the room thermostat will be reset and  
restore the device to factory default settings.  
»CONNECTION PLAN  
JOY Fancoil 5DO (85..260 V ~)  
JOY Fancoil EC AO2DO (85..260 V ~)  
JOY Fancoil EC 3AO (24 V ~/=)  
1 Fan Speed 3  
1 EC Fan GND  
1 Digital Input 2  
2 Fan Speed 2  
3 Fan Speed 1  
4 Cooling  
2 EC Fan (0..10 V)  
2 EC Fan (0..10 V)  
3 Cooling (0..10 V) or 6-way valve  
4 Heating (0..10 V) or 6-way valve  
5 GND DI 2  
4 Cooling  
5 Heating  
5 Heating  
6 Digitaler Input 2 (230 V)  
7 L  
8 N  
6 Digital Input 2 (230V)  
7 L  
8 N  
6 GND  
7 24 V = (±10%) or 24 V ~ (±10%)  
8 GND  
12 GND DI 3  
12 GND DI 3  
12 GND DI 3  
11 Digital Input 3  
10 GND DI 1  
11 Digital Input 3  
10 GND DI 1  
11 Digital Input 3  
10 GND DI 1  
9 Digital Input 1 (or NTC10K)  
9 Digital Input 1 (or NTC10K)  
9 Digital Input 1 (or NTC10K)  
Note: Parallel connection of the potential-loaded inputs is not permitted!  
If the operating mode (change-over DI) of several devices is to be switched together by one contact, the potential-free 230V input must be used  
(DI2, only possible with the 230V version). It must be ensured that the same phase is used for jointly switched devices.  
JOY_Fancoil_Datasheet_en © 2023  
GeneralDetails
Namethermokon JOY 5DO Digital Room Thermostat User Manual
Makethermokon
LanguageEnglish
FiletypePDF (Download)
File size0.53 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide
thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide

thermokon JOY 5DO Digital Room Thermostat User Manual