Home > thermokon > thermokon JOY 5DO Digital Room Thermostat User Manual

thermokon JOY 5DO Digital Room Thermostat User Manual

Page 2 / 8  
Issue date: 22.06.2023  
»PRODUCT TESTING AND CERTIFICATION  
Declaration of conformity  
»NOTES ON DISPOSAL  
As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as  
part of a building or a structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic  
Act (WEEE) is not applicable. However, most of the products may contain valuable materials that should be recycled  
and not disposed of as domestic waste. Please note the relevant regulations for local disposal.  
»MOUNTING ADVISE ROOM SENSORS  
The Accuracy of the room sensors are influenced by the technical specifications as well as the positioning and the installation type.  
During Assembly:  
•
•
•
Seal mounting box (if present).  
Installation type, air draught, heat source, radiation heat or direct sunlight can affect the measurement.  
Bulding material specific properties of the installation place (brick-, concrete-, partition wall, cavity wall, …) can affect the measurement.  
(e.g.: Concrete accepts room temperature variation slower than cavity walls)  
Assembly not recommendet in…  
•
•
•
•
Air draught (e.g.: close to windows / doors / fans …)  
Near heating sources,  
Direct sunlight  
Niches / between furniture / …  
»MOUNTING ADVICE JOY  
Plasterboard boxes shall be covered by wall paper or paint to avoid that the plasterboard box's front rim will be partially visible underneath JOY.  
Maybe consider using white plasterboard boxes (i.e. Kaiser 9063-77).  
»APPLICATION NOTICE  
Software  
MicroSD-Card  
Data storage device for Update, Upgrade or configuration  
- FAT-filesystem required  
- NTFS and exFAT filesystems are not supported!  
Bootloader  
A MicroSD-card Bootloader for loading applications (Update, Upgrade) or configurations is integrated in the device.  
active bootlader = ring illumination blinks (1 sec. cycle), display is not triggered!  
Firmware  
Update  
- Remove upper part, insert a microSD-card with valid Update file, mount upper part.  
- Valid update file is recognized and the update process is started (ring illumination blinks in a 300ms cycle)  
- New application is started automatically after Update (approx. 20-30 sec.).  
- Remove upper part, to remove MicroSD-card from the device!  
Device  
Configuration  
- Remove upper part, insert a microSD-card with device configuration file, mount upper part.  
- Configuration file is recognized and the device is configured.  
- Device ready for operation.  
- Remove upper part, to remove MicroSD-card from the device!  
The parameters for the display, set point and the controller can only be changed via the configuration software.  
»NOTES ON THE UPDATE FUNCTION  
An update of the device software is only possible within the version main numbers.  
3.0.2 ► 3.0.11  
2.6.6 ► 2.3.0  
2.x ► 3.x  
2.x ► 1.x  
»CONFIGURATION VIA UCONFIG | MICRO SD-CARD  
Configuration software:  
uConfig | Windows 10 is required to use the uConfig configuration software  
The JOY room thermostat can be parameterised using the uConfig configuration software. An SD card is used to transfer the  
created configuration file to the device.  
The installer for the configuration software can be found in the Download-Section on our website. The installer retrieves all  
necessary files and plug-ins from our web server. In this version an update function is integrated in the software.  
Download-Section  
JOY_Fancoil_Datasheet_en © 2023  
GeneralDetails
Namethermokon JOY 5DO Digital Room Thermostat User Manual
Makethermokon
LanguageEnglish
FiletypePDF (Download)
File size0.53 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide
thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide

thermokon JOY 5DO Digital Room Thermostat User Manual