»MENU → COMMON SETTINGS  
Menu  
Timechannel  
Time/Date  
Sensor settings  
Common settings  
EnOcean list  
EnOcean configuration  
Common device settings:  
Brightness  
Valve protection  
ECO deadband  
Fanstages  
Valve protection  
A valve protection function actuates the heating and cooling valves  
regularly to prevent locking during non-usage times.  
The function is executed fridays at 11.00 (heating valve) and 11.15  
(cooling valve). The corresponding valve is triggered for 5 minutes, if not  
activated during the last 96 hours.  
Language  
Factory setting (reset)  
ECO deadband  
Brightness  
The dead band can be adjusted (default 10.0 K)  
* further information in the software specification file  
Configuration of the LCD brightness/ LED ring brightness during button  
operation/ usage.  
Factory setting  
By selecting “Factory setting”, the room thermostat will be reset and  
restore the device to factory default settings.  
»MENU → ENOCEAN LIST  
In this list, all channels with the taught-in sensors or actuators are displayed.  
Menu  
Timechannel  
Time/Date  
Sensor settings  
Common settings  
EnOcean list  
EnOcean configuration  
After selecting a device further information are displayed.  
»MENU → ENOCENAN CONFIGURATION  
In this menu item, the radio channels can be configured and individual information can be called up.  
Menu  
Timechannel  
Time/Date  
Sensor settings  
Common settings  
EnOcean list  
EnOcean configuration  
EXIT  
DELETE CHANNEL  
SET ACTOR  
SHOW CHANNEL  
In the footer, various menu items can be selected with the LEFT / RIGHT keys and the corresponding menu item is selected with the ENTER key.  
SAB valve actuators are learned in with the function <SET ACTOR>  
The access to the menu <EnOcean configuration> can be protected with a password via Modbus. The login  
remains unlocked in the EnOcean menu until 10 minutes after the last key press. Default password: 2030  
More detailed information for the configuration of the EnOcean channels can be found in the specification.  
There are 20 channels available that can be assigned different functions. A channel can be configured as a receive channel, as a send channel or  
as a message server (SAB communication).  
6 channels can be configured with SAB valve actuator, one of these can be set with the bath function. For the SAB with the bath function, an  
additional setpoint offset can be set. If SAB valve actuators are learned in, the analogue outputs to the internal controller remain active and can  
also be used.  
JOY_SR Fancoil_Modbus_Datasheet_en © 2023  
GeneralDetails
Namethermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide
Makethermokon
LanguageEnglish
FiletypePDF (Download)
File size0.59 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
thermokon JOY 5DO Digital Room Thermostat User Manual
thermokon JOY 5DO Digital Room Thermostat User Manual

thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide