»FUNCTION DESCRIPTION – BUTTONS  
On the touch surface, there are adjustment options for setpoint and fan speed regulation.  
While pressing these buttons, the white ring-LED of the Power-button lights up for visual feedback.  
Fan speed adjustment: „fan speed Setpoint change (setpoint range  
up“ / „fan speed down“ ± 3 °C, default, configurable).  
Power button for Standbymode,  
or Presence key*  
*If the key is used as a  
presence key at the same time,  
the key must be pressed for at  
least 3s, in all other cases a  
short press is sufficient.  
3 seconds without any interaction, the display returns back to main screen.  
Standby mode (not compatible with Keycard-switch function)  
In standby mode the display and all outputs are switched off (controller deactivated). The frost and heat protection monitoring remains active. The  
Modbus registers can still be read out (e.g. room temperature).  
Navigation Parametermenu  
(up, down, left, right)  
Open submenu (right)  
In header left to leave the submenu  
Confirmation  
»DIAGNOSTICS MENU  
To access the diagnostics menu, select the header in the startscreen of the parameter menu, and press the ENTER key. Here you will find various  
information, such as device type, software version, state of the inputs and outputs and controller state (current manipulated variable).  
»PARAMETER MENU – MODBUS INTERFACE  
The configuration menu is activated by simultaneously pressing the buttons “up” (A) and “down” (C) for at least 5 seconds.  
The menu is enabled during the first 60 minutes after switching on the supply voltage as long as the device is not actively involved in Modbus  
communication. As soon as the device receives a valid request addressed to the device from a DDC, access to the menu is blocked. Without valid  
communication, access is blocked after 60 minutes!  
Modbus settings  
Address  
Baudrate  
Parity  
-/+  
-/+  
-/+  
32  
19200  
Even  
Address (default: 32)  
Adjustable address (1-247)  
Baud rate (default: 19200)  
9600Bd | 19200Bd | 38400Bd | 57600Bd  
Parity (default: even)  
Non | odd | even  
JOY_SR Fancoil_Modbus_Datasheet_en © 2023  
GeneralDetails
Namethermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide
Makethermokon
LanguageEnglish
FiletypePDF (Download)
File size0.59 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
thermokon JOY 5DO Digital Room Thermostat User Manual
thermokon JOY 5DO Digital Room Thermostat User Manual

thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide