Danfoss RT 103 Thermostat Installation Guide
Installation guide
Thermostat
RT 103, RT 140, RT 141
RT 101
089
Fig. 1
Fig. 2
Fig. 3
RT 103
RT 140
RT 141
Fig. 4
differential adjusting nut (19) to the value
indicated by the use of the nomogram in
fig. 4. The maximum operating pressure is
thus the sum of the setting temperature
and the differential.
INSTALLATION
ENGLISH
Et sæt Pg13,5 kabelforskruning er vedlagt
produktet i en separat pose. For at sikre
kapslingsgrad IP66 (enheder med automa-
tisk reset) eller IP54 (enheder med ekstern
DANSK RESET) er det nødvendigt at mon-
tere denne kabelforskruning som vist i fig. 3.
Hvis denne kabelforskruning ikke bruges
sammen med et kabel, bør der monteres
en blindprop (metal skive).
Thermostats Types RT 103, RT 140, RT 141
Fig. 1, 2 and 4
Ambient temperature: -50 °C – 70 °C
Maximum sensor temperature:
RT 103: 100 °C
Example
RT 140: 240 °C
RT 141: 250 °C
It is desired to control an air heater by the
use of an RT 103.
Maximum discharge temperature: 32 °C
Minimum discharge temperature: 30 °C
Differential: 32 °C - 30 °C = 2 °C
INSTALLATION
INDSTILLING
Fig. 4
A. Områdeindstilling
B. Opnået differens
C. Differensindstilling
Termostaten indstilles efter den funktion
- slutte eller bryde - som skal ske ved
faldende temperatur (områdeindstilling).
Selve indstillingen udføres med håndknap-
pen (5) under samtidig aflæsning af
hovedskalaen (9).
Differensen indstilles med differensrullen
(19) efter nomogrammet i figur 4. Højeste
funktionstemperatur er således lig summen
af indstillingstemperatur og differens.
A set of Pg13.5 cable gland is attached to
the RT in a separate bag. To ensure IP66
(units with automatic reset) or IP54 (units
with external reset) grade of RT enclosure
it is necessary to assemble this gland as
shown in the fig. 3. If this gland is not used
with a cable, a metal blinding should be
also assembled.
1. Connect the heater to terminals 1-2 of
the thermostate
2. Set the thermostate for 30 °C by
rotating the knob (5)
3. Set the differential adjusting nut (19) at
the figure 4 which is found by reading
the nomogram for RT 103 in fig. 4.
DANSK
SETTING
Fig. 4
A. Range setting
Termostater Type RT 103, RT 140, RT 141
Fig. 1, 2 og 4
B. Differential obtained
C. Differential setting
The thermostat is set by rotating the knob
(5), at the same time reading the main
scale (9).
Omgivelses temperatur: -50 °C – 70 °C
Max. følertemperatur:
RT 103: 100 °C
RT 140: 240 °C
RT 141: 250 °C
Eksempel
En varmluftovn ønskes styret af en RT 103.
Max. afgangstemperatur: 32 °C
The differential is set by rotating the
AN16198643545801-000202 | 1
© Danfoss | Climate Solutions | 2021.07
| General | Details |
|---|---|
| Name | Danfoss RT 103 Thermostat Installation Guide |
| Make | Danfoss |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.43 MB |

Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide

Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide

Danfoss UT 72-UT 73 Universal Thermostat Installation Guide

Danfoss ECtemp 530 Electronic Thermostat Installation Guide

Danfoss 014G0251 Eco Radiator Thermostat User Guide

Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide

Danfoss RET230P Electronic Thermostat Instruction Manual

Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide

Danfoss RET1000 Series Electronic Thermostat User Guide

Danfoss RT 103 Thermostat Installation Guide Overview
Summary of Contents
- Page 1: Installation guide Thermostat Types RT 103, RT 140, RT 141 To ensure IP66 or IP54 grade of RT enclosure, it is necessary to assemble the cable gland as shown in fig. 3. If the cable gland is not used with a cable, a metal blinding should also be assembled. Ambient temperature: -50 °C – 70 °C Maximum sensor temperature for RT 103 is 100 °C. The thermostat is set by rotating the knob (5), while reading the main scale (9). The differential is set by the differential adjusting nut (19) according to the nomogram in fig. 4. Maximum discharge temperature is 32 °C and minimum discharge temperature is 30 °C. The highest function temperature is the sum of the setting temperature and the differential. Connect the heater to terminals 1-2 of the thermostat.
- Page 2: Min. afgangstemperatur: 30 °C Thermostats Types RT 103, RT 140, RT 141 Température ambiante: -50 °C – 70 °C Max. Fülertemperatur: RT 103: 100 °C, RT 140: 240 °C, RT 141: 250 °C Indstil termostaten på 30 °C med håndknappen (5) Indstil differensrullen (19) på tallet 4 Un ensemble presse étoupe Pg13.5 est joint au RT dans un sac séparé Pour assurer l’indice IP66 du RT ou IP54, il faut assembler le presse étoupe Der Thermostat ist nach der Funktion - Schliessen oder Öffnen, - einzustellen Die Differenz wird mit der Differenzrolle (19) nach dem Nomogramm in Abb. 4 eingestellt.