thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide
Page 2 / 11
Issue date: 01.05.2023
»NOTES ON DISPOSAL
As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as
part of a building or a structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic
Act (WEEE) is not applicable. However, most of the products may contain valuable materials that should be recycled
and not disposed of as domestic waste. Please note the relevant regulations for local disposal.
»MOUNTING ADVISE ROOM SENSORS
The Accuracy of the room sensors are influenced by the technical specifications as well as the positioning and the installation type.
During Assembly:
•
•
•
Seal mounting box (if present).
Installation type, air draught, heat source, radiation heat or direct sunlight can affect the measurement.
Bulding material specific properties of the installation place (brick-, concrete-, partition wall, cavity wall, …) can affect the measurement.
(e.g.: Concrete accepts room temperature variation slower than cavity walls)
Assembly not recommendet in…
•
•
•
•
Air draught (e.g.: close to windows / doors / fans …)
Near heating sources,
Direct sunlight
Niches / between furniture / …
»MOUNTING ADVICES
Plasterboard boxes shall be covered by wall paper or paint to avoid that the plasterboard box's front rim will be partially visible underneath JOY.
Maybe consider using white plasterboard boxes (i.e. Kaiser 9063-77)
»APPLICATION NOTICE
Software
MicroSD-Card
Storage medium to be used for update, upgrade or configuration, parameterization receive channels.
- Formatting in FAT file system required
- NTFS and exFAT file systems are not supported!
- Read in/out Enocean configuration
Bootloader
A MicroSD card bootloader for applications (update, upgrade) or configurations is integrated in the device.
Active bootloader = ring illumination flashes (1 sec. cycle), display is not activated.
Firmware Update - Remove upper part, insert MicroSD card with valid update file, place upper part on lower part.
- Valid update file is recognized and update process is started (ring illumination flashes at 300ms intervals).
- New application is started after update (approx. 20-30 sec.).
- Remove upper part to remove MicroSD card from device!
Device
Configuration
- Remove upper part, insert MicroSD card with device configuration file, place upper part on lower part.
- Configuration file is recognized and device is configured
- Device ready for operation
- Remove upper part, remove MicroSD card from device, place upper part on lower part.
Note: The parameters for the display, the setpoints and the controller can only be changed via the
configuration software.
Enocean
Configuration
- Remove upper part, insert MicroSD card with Enocean configuration file, place upper part on lower part.
- Configuration file is recognized and device is configured
- Device restarts after update.
- Device ready for operation
- Remove upper part, remove MicroSD card from device, place upper part on lower part.
Save Enocean
- Remove upper part, insert empty microSD card, place upper part on lower part.
Configuration on - Device starts
MicroSD-Card - Configuration file is saved on MicroSD card
- Remove upper part, remove MicroSD card from device, place upper part on lower part.
Note: EasySens receivers (SAB valve actuators or actuators, SRC/STC-x) still require the ID of the
transmitter (Joy) via manually triggered teach-in telegram.
»UPDATE FUNCTION ADVICE
An update of the device software is only possible within the version main numbers.
3.0.2 ► 3.0.11 2.6.6 ► 2.3.0 2.x ► 3.x
2.x ► 1.x
JOY_SR Fancoil_Modbus_Datasheet_en © 2023
| General | Details |
|---|---|
| Name | thermokon JOY SR 5DO Electronic Fancoil Thermostat User Guide |
| Make | thermokon |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.59 MB |

thermokon JOY 5DO Digital Room Thermostat User Manual