SUNRICHER SR-ZG9092A Zigbee Heating Thermostat Installation Guide
Insert the power and heater wires to the correct device terminals by inserting a small Phillips-head screwdriver in the slot beneath
each terminal to open. Follow the connection diagram and instructions below:
5.2.8 Time-0x000A(client)
The Time cluster is a general cluster for time it is based on a UTC time in seconds since 0 hrs 0 mins 0 sec on
1st January 2000. Refer to [Z2] for ZigBee specification of the time cluster.
The metering device will use this clusters as a client – provided that a suitable Time Server is available on the
network (most likely on the Gateway/concentrator)
• Power wires: connect Line & Neutral wires to L & N terminals labeled “IN”
• Heater wires: connect Line & Neutral wires to L & N terminals labeled with “heating element” graphic
WARNING: The wire size shall be in compliance with regulations, using wire with insufficient size for big load will cause
severe temperature rising.
If the device has bound TIME cluster, then the device will acquire the value of Local Time (0x0007)
spontaneously.
Connection diagram 1
Connection diagram 2
L
N
L
N
5.2.9 OccupancySensing-0x0406(client)
The attributes that can be received:
Type
Description
Attribute
Occupancy
Bit 0 specifies the sensed occupancy as follows: 1 = occupied, 0 = unoccupied.
This flag bit will affect the Occupancy attribute of HVAC cluster, and the
operation mode.
bitmap8 ,
0x0000
SR-ZG9092A
SR-ZG9092A
5.3 Application Endpoint #2–OTA
NTC
L
L
N
N
NTC
L
L
N
N
supported
server
Description
Cluster
0x0000
0x0003
Basic
server
Identify
O
T
A
U
p
g
r
a
d
e
Pull-oriented firmware upgrade. Searches the network for mating servers and
allows the server to control all stages of the upgrade process, including which
image to download, when to download, at what rate and when to install the
downloaded image.
0x0019
Client
Floor temp
sensor
Floor temp
sensor
Ota complies to standard Zigbee protocol.
5.4 Application Endpoint #242 –GreenPower
Troubleshooting:
7. Installation
2)ꢀRelease the frame
1) Release front cover by inserting a flat screw-driver into side crack
1. External (floor) sensor temperature tolerance is too high
Possible reason: the selected sensor type is not correct
2. The gateway can not set temperature when energy save mode is selected
The temperature schedule of auto mode (energy save mode) is not configured correctly
3. Current temperature is not executed when away mode is selected
Check whether away mode time is set as 0 or within valid time range
4. Over heat alarm when power on the device
Possible reason: the set sensor type is not correct or sensor type after factory reset is not correct
5. Device time is not the same as the gateway controller after added to the network
Set the device time and time zone manually after added to the gateway network
6. The tolerance of the indoor temperature sensor is high after powered on
Possible reason: due to temperature effect, we need to wait for a while
3) Mount back part into junction box, then screw the thermostat in
4) Re-install the frame and the front part in sequences
6.Wiring diagram
This device should be installed by a licensed electrician in a manner that conforms to local regulations and building codes.
Provide these instructions to the licensed electrician who is installing the device.
WARNING: Electrical power must be switched off during installation.
1. Placement of the device is of utmost importance for proper operation and must be away from sunlight and sources of direct
heat. We recommend installing the device approximately 1.5 meters above the floor.
2. Remove the display unit and backplate of the device from the packaging.
3. FIRST ENSURE THE POWER IS OFF at the main circuit breaker, and then test the wires with a probe or multimeter to verify.
| General | Details |
|---|---|
| Name | SUNRICHER SR-ZG9092A Zigbee Heating Thermostat Installation Guide |
| Make | SUNRICHER |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.88 MB |