SUNRICHER SR-ZG9092A Zigbee Heating Thermostat Installation Guide
int16S ,
reportable OutdoorTemperature
SceneValid
0x0001
0x0002
bool,
read-only
This is floor temperature, the maximum resolution this format allows is 0.01 ºC.
0x0003
0x0004
If true, the scene identified by CurrentGroup and CurrentScene is currently
active, i.e. all device attribute values match the values in the scene field set.
read-only
Occupancy
bitmap8 ,
read-only
When this flag is set as 1, it means occupied, OccupiedHeatingSetpoint will be
used, otherwise UnoccupiedHeatingSetpoint will be used.
bitmap8 ,
read-only
NameSupport
LocalTemperatureCalibration
Command supported:
Int8S ,
Room temperature calibration, range is -30-30, the maximum resolution this
format allows 0.1°C. Default value: 0
0x0010
0x0011
reportable
Command
Description
Add Scene
int16S ,
OccupiedCoolingSetpoint
0x00
0x01
0x02
0x03
Adds a scene with or without a scene field set
reportable
This system is not invalid.
View Scene
OccupiedHeatingSetpoint
int16S ,
Returns the scene field set, name and transition times for a scene.
Range is 0-4000,the maximum resolution this format allows is 0.01 ºC. Default
is 0xbb8(30.00ºC)
0x0012
0x0014
reportable
Remove Scene
Removes a scene from the scene table.
UnoccupiedHeatingSetpoint
int16S ,
Range is 0-4000,the maximum resolution this format allows is 0.01 ºC.
Default is 0x258(6.00ºC)
Remove All Scenes
reportable
Removes all scenes that belong to a particular group.
Store Scene
Enum8,
ControlSequenceOfOperation
0x001B
0x0029
0x04
0x05
Stores the device’s current state as a scene or updates a previously stored
scene accordingly
reportable
Set device supported operation type, here only supports Heating Only(0x02)
Map16,
HVAC relay state/ ThermostatRunningState
read-only,
reportable
Recall Scene
Indicates the relay on/off status, here only supports bit0( Heat State)
Reverts the device’s current state using the values from the previously
stored field set.
Proprietary Attributes:
5.2.3 Groups-0x0004 (Server)
Manufacturer
Description
code
Type
Attribute
Attributes supported:
Type
Description
Attribute
OperateDisplayLcdBrightnesss
OLED brightness when operate the buttons:
bitmap8,
read-only
NameSupport
ENUM8,
0x0000
Value=0 : Low Level
0x1000
0x1224
0x1224
0, not supported
reportable
Value=1 : Mid Level(default)
Value=2 : High Level
Command supported:
ButtonVibrationLevel
Key beep volume & vibration level:
Value=0 : off(default)
Command
Description
ENUM8
Add Group
0x1001
0x00
0x01
reportable
Adds the endpoint to a group.
Value=1 : Low Level
Value=2 : High Level
View Group
Determines whether the device belongs to a group and returns the group
name, if supported
FloorSenserType
Select external (Floor) sensor type:
Value=5 : NTC 12K/25
Remove Group
ENUM8
Removes this endpoint from the specified group. Also removes all scenes
that refer to this group.
Value=4 : NTC 100K/25
Value=3 : NTC 50K/25
0x03
0x1002
0x1224
reportable
Value=2 : NTC 15K/25
Remove All Groups
Value=1 : NTC 10K/25 (Default)
Removes this endpoint from all groups. Also removes all scenes that refer to
any of the existing groups.
0x04
0x05
ControlType
The referring sensor for heat control:
Value=0 : Room sensor(Default)
Value=1 : floor sensor
Add Group if Identifying
ENUM8
0x1003
0x1004
0x1224
0x1224
Adds this endpoint to the group, if the endpoint is identifying.
reportable
Value=2 : Room+floor sensor
5.2.4 Thermostat-0x0201(Server)
Attributes supported:
PowerUpStatus
ENUM8
The mode after reset power of the device:
Value=0 : default mode
Type
Description
Attribute
reportable
int16S ,
reportable LocalTemperature Attribute
0x0000
Value=1 : last status before power off (Default)
read-only
This is room temperature, the maximum resolution this format allows is 0.01 ºC.