Cooling Calibration
Step 1 —
Remove the cover using the 192-632 Verify that the supply pressure is 18 to 25 psi (124
Step 2 —
Calibration Tool. Verify that the room to 172 kPa). Set the cooling dial to room
temperature is between 70°F and
80F (2°C and 27C).
temperature by turning the exposed adjustment
knob or using a hex key as shown. Allow the
thermostat to stand for about five minutes to
adjust to the new setting.
Step 3 —
Step 4 —
Moisten the needle and insert the
192-633 Test Gauge and needle
adapter in the test port. Read the
control pressure.
If the control pressure does not read 7 to 8 psi (48
to 55 kPa), turn the calibration screw using the
192-632 Calibration Tool or a 1/8-inch (3.2 mm)
wrench until the pressure is 7 to 8 psi (48 to
55 kPa). The sensing element is now in
calibration and the setpoint can be changed to the
desired room temperature.
Page 8
Siemens Industry, Inc.
| General | Details |
|---|---|
| Name | SIEMENS TH 193 HC Heating and Cooling Room Thermostat Instruction Manual |
| Make | SIEMENS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.15 MB |

SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual

SIEMENS RDG400 Room Thermostat Instruction Manual

SIEMENS M3182 Room Thermostat Instruction Manual

SIEMENS RDS120-B Smart Thermostat Instructions

SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual

SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual

SIEMENS RDH100RF/SET Room Thermostat Instruction Manual

SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide

SIEMENS RS485 Flush Mounted Room Thermostat User Manual

SIEMENS RDG260KN Room Thermostat Instruction Manual