SIEMENS TH 193 HC Heating and Cooling Room Thermostat Instruction Manual

Free Energy Band TH 193 HC Heating/Cooling Room Thermostat  
Technical Instructions  
Document Number 155-068P25  
February 14, 2022  
Control action  
See Table 1  
Specifications  
Operating ranges  
45°F to 85°F (7°C to 30°C)  
30 psi (207 kPa)  
Supply air pressure, maximum  
Normal air supply pressure  
Sensitivity adjustment  
18 to 25 psi (124 to 172 kPa)  
1 to 4 psi/°F (12 to 50 kPa/°C)  
Nominal air consumption  
One-pipe  
Two-pipe  
25 scim (6.8 ml/sec) per side  
230 scim (63 ml/sec) per side  
Temperature response  
Temperature  
0.1°F (0.06°C)  
Storage temperature  
Ambient operating temperature  
-10°C to 140°F (-23°C to 60°C)  
40°F to 140°F (4°C to 60°C)  
Dial graduations  
Factory settings  
2°F (1°C)  
Calibration @ 72°F (22°C)  
Sensitivity  
Limit stop adjustment  
7.5 psi (52 kPa)  
2.5 psi/F (31 kPa/C)  
45°F and 85°F (7°C and 30°C)  
Standard cover  
Shipping weight  
Dimensions  
Cycolac, Desert Beige  
0.7 lbs. (0.3 kg)  
See Figure 10  
Accessories  
See the following Technical Bulletins for information on accessories:  
Technical Bulletin  
Document Number  
TB 237 Terminal Kits  
TB 214 Adapter Kits  
TB 193 Guard Kit  
TB 241 Test Head Kit  
TB 167 Restrictors  
155-244P25  
155-231P25  
155-222P25  
155-255P25  
155-213  
Operation  
The TH 193 HC thermostat is a two-temperature thermostat with two separate outputs.  
In direct acting control, an increase in temperature increases the control air pressure  
and a decrease in temperature decreases the control pressure. In reverse acting  
control, an increase in temperature decreases the control air pressure and a decrease  
in temperature increases the control pressure.  
The TH 193 HC provides two separate bimetal elements; one for heating mode and the  
other for cooling mode. The setpoint of the two elements determines the window of the  
dead band. A 4F (2C) minimum dead band is standard, where the heating mode  
setpoint is 72F (22C) and the cooling mode setpoint is 78F (26C). Figure 4 shows a  
typical application with setpoints adjusted for a 6F (4C) dead band.  
Figure 5 shows direct acting TH 193 HC output characteristics. As heating increases,  
the output pressure increases from 0 to 15 psi (0 to 103 kPa). A field adjustable dead  
band occurs. When the dead band elapses, cooling occurs from 0 to 15 psi (0 to  
103 kPa).  
Siemens Industry, Inc.  
Page 5  
GeneralDetails
NameSIEMENS TH 193 HC Heating and Cooling Room Thermostat Instruction Manual
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size0.15 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS TH 193 HC Heating and Cooling Room Thermostat Instruction Manual