Home > RET > RET-230-HC-3 Electronic Heat Cool Thermostat User Manual

RET-230-HC-3 Electronic Heat Cool Thermostat User Manual

Product overview  
The thermostat is primarily designed for use in systems  
equipped with 4-pipe fan-coil units. It may also be used in  
other heat / cool systems, including split systems and air to  
air heat-pumps.  
The thermostat controls room temperature by sequencing  
the operation of heating and cooling. A selectable dead-band  
prevents overlap of heating and cooling processes. For  
systems equipped with compressor derived cooling, including  
heat-pumps, a selectable compressor delay timer is also  
included. If used to control a heat-pump, the reversing valve  
can be energisation on either a heat or cool demand.  
Installation  
First remove the wallplate from the back of the unit.  
Ensure that there is a minimum of 50mm above the  
unit and 100mm below the unit in order to mount the  
plug-in module.  
Fix at a height of  
approximately 1.5m  
from the oor, away  
from draughts or heat  
sources such a fan-coil  
outlets, sunlight or ofce  
equipment.  