PECO T8168 Performance Pro Thermostat Installation Guide

540  
600  
Factory Default Reset  
0- Disable (Default)  
When enable is selected he device will return to factory default settings.  
1- Enable  
Cooling System Output  
Test  
0- Disable (Default)  
Cool Operation is enabled and the associated output based on Service Menu 110. The  
output is activated for 10 minutes. The 24VAC and 0-10 VDC Fan output will automatically  
turn on.  
1- Stage 1 Cooling/ Y1 and YD  
2 – Stage 2 Cooling/ Y1, Y2 and YD  
0- Disable (Default)  
610  
620  
Heating System Output  
Test  
Heat Operation is enabled and the associated output based on Service Menu 110. The  
output is activated for 10 minutes. The 24VAC and 0-10 VDC Fan outputs will automatically  
turn on.  
1- Stage 1 Heating/ W1 and WD  
2 – Stage 2 Heating/ W1, W2 and WD  
0- Disable (Default)  
Fan System Output Test  
If enabled is selected it will activate Based On Service Menu 110. The output will be enabled  
for 10 minutes.  
1- Enable Fan HI Outputs/ G and GD  
2 – Enable Fan LO Outputs/ G1 and GD  
3 - Enable Fan MED Outputs/ Y2 and GD  
4 – Enable GD High Fan  
5 – Enable GD MED Fan  
910  
920  
IP Address  
Displays Current IP Address  
Requires Thermsotat Configuration  
Thermostat will show “000”, if unconfigured.  
On entry, the BACnet IP address will be displayed in 4 sets of 3 digits. The UP arrow is used  
to cycle through the IP segments. All leading zeros are removed.  
Example:First IP segment displayed: 192, Press “UP”  
Second IP segment displayed: 010, Press “UP”  
Third IP segment displayed: 128, Press “UP”  
Fourth IP segment displayed: 001  
The IP Address in this example is “192.10.128.1”  
MSTP Address  
Displays current MSTP address.  
Requires Thermsotat Configuration  
On entry, the BACnet MSTP address is displayed. If unconfigured is will show”000”  
930  
950  
Device ID  
Displays Current Device ID  
Set to 1  
Displays 2 set of 2 digits using UP and DN arrows.  
Wi-Fi Reset  
Unit enters AP Mode and broadcasts SSID “T8168XXXX”  
TROUBLESHOOTING & FREQUENTLY ASKED QUESTIONS  
Symptom  
Potential Cause(s)  
Solution  
If display screen is blank  
• Thermostat is not being powered  
• Check to assure proper wiring of power to (24 VAC-1) and (24 VAC-2) .  
• Check power to verify that there is 24 VAC available.  
• Default Display is set to “4” (None)  
• Keypad Lockout may be enabled  
• Check Service Menu 520.  
If keys do not allow manual entry  
Service Menu does not display  
• Access Service Menu 340. Within this menu, select option “0” to assure  
there is no keypad lockout (so manual entry is enabled).  
• PIN access is enabled  
• Buttons were not pressed simultaneously  
• Access requires the three digit code set by the installer.  
• Wait for unit to return to default display and retry.  
Err In Clock Dispay  
Door in Clock Display  
Fdd in Clock Display  
• Indicates a service fault input  
• Indicates service is required. See SM 175  
• Close door and /or window to clear fault.  
• Indicates service is required. See SM 175  
• Door or window is open  
• Indicate an economizer or other system fault  
If no heating or cooling is running, but there is a call  
for heat or cool (Heat/Cool appears on display) in  
Auto mode  
• Heating or cooling equipment is not operating  
• Minimum off time has not been met  
• Check Service Menu 110 to assure that the correct option is selected to  
match the system type.  
• Check wiring, using output tests to verify (see Service Menus 600, 610,  
620).  
If heating or cooling system doesn’t respond  
• System type selection is incorrect  
• System type selection is incorrect  
• Check Service Menus 110 and 120 to assure that the correct option is  
selected to match the system type.  
If heating and cooling equipment are running at the  
same time  
• Check Service Menu 110 to assure that the correct option to match the  
system type is selected.  
• Verify wiring connections  
• Separate the heating and cooling wires, using output tests to verify (see  
Service Menus 600, 610, 620).  
If Demand Indicator light is red  
• Heating is occurring  
• No action is required.  
• No action is required.  
If Demand Indicator light is green  
Fan outputs turned off after 3-minutes  
• Cooling system is running  
• Pipe sensor is connected and water  
temperarture between hot and cold set points  
• Building Boiler or Chillers may be turned off.  
• See Service Menus 171, 172, 173 & 174  
Menu Item Not available  
• Some service menus are disabled when not in  
use or feature is not available.  
• Verify system type selection and feature selection is correct.  
Red LED is Flashing and code is in clock location  
• Fault is present on SC and S1 input  
• Check SM175 for code  
• If using a remote sensor, verify probe wiring.  
© COPYRIGHT 2025 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74599 3220-2406 REV 02  
8
GeneralDetails
NamePECO T8168 Performance Pro Thermostat Installation Guide
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.47 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T372P Thermostat Instruction Manual
PECO T372P Thermostat Instruction Manual
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide
PECO TW180 Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual

PECO T8168 Performance Pro Thermostat Installation Guide