Home > PECO > PECO T8168 Performance Pro Thermostat Installation Guide

PECO T8168 Performance Pro Thermostat Installation Guide

120  
122  
Fan Control (Heating)  
0 – OFF for Heating (Gas/Oil Heat)  
1= Electric Furnace (DEFAULT)  
0 = 4 – 20mA  
0: The thermostat will not activate the fan with a heating demand.  
1: The thermostat will activate the fan with heat demand.  
YD Output Configuration  
Configures digital cooling output for 0-10VDC or 4-20mA DC  
Configures digital heating output for 0-10VDC or 4-20mA DC  
1 = 0 – 10 Volts (DEFAULT)  
WD Output Configuration 0 = 4 – 20mA  
1 = 0 – 10 Volts (DEFAULT)  
0 = 4 – 20ma  
1 = 0 – 10 Volts (DEFAULT)  
GD Max Voltage, Heating 6 – 10 VDC (Default: 8)  
Demand 12 – 20 mA (Default: 20)  
GD Max Voltage, Cooling 6 – 10 VDC (Default: 10)  
123  
124  
GD Output Configuration  
Configures digital fan output for 0-10VDC or 4-20mA DC  
125  
126  
127  
135  
Depending on SM 124 setting, sets Fan HI speed voltage or current (mA) at terminal GD with  
demand for Heat.  
Depending on SM 124 setting, sets Fan HI speed voltage or current (mA) at terminal GD with  
demand for Cool.  
Demand  
12 – 20 mA (Default: 20)  
GD Min Voltage  
0 – 6 VDC (Default: 2)  
4 – 12 mA (Default: 4)  
Depending on SM 124 setting, sets Fan LO speed voltage or current (mA) at terminal GD  
with no demand.  
W1 Output Configuration  
S1 Remote Sensor Input  
0 - NC: Normally Closed Operation (Default)  
1 - NO: Normally Open Operation  
Reverses the ON/OFF operation for W1. NC operation powers on with a demand. NO  
opreation powers off with a demand and will be on with no demand unless main power is  
removed from the thermostat.  
170  
171  
0= No Remote Sensors (Default)  
0: Remote temperature sensing is disabled.  
1: The T8168 uses the remote sensor only for temperature sensing.  
2: The T8168 averages the local and remote sensor for temperature sensing.  
When using a remote sensor an open or short will turn off outputs and display either  
2Ero(open) or 2Erc (closed). Fault detection settings are not used.  
1= Remote Indoor Sensor Connected  
2 = Remote Sensor Connected And Sensor  
Averaging  
S2 Pipe Sensor  
0 – Disabled (Default)  
1 – Two Pipe Operation  
Enables fan coil pipe sensor operation. Connect a PECO pipe sensor or dry switch closure for  
change over from Summer (cold water) to Winter (hot water). 2-pipe operation uses the Cool  
1 output for heating and cooling. Heat 1 is disabled. 4-pipe operation allows heat 1 in summer  
mode of operation.  
2 – Four Pipe Operation (use for 2-pipe with  
electric heat relay)  
Available when SM 110 = 1 through 5 or 14 through 16  
172  
173  
174  
Pipe Sensor Threshold for 50F to 72F (Default 60F)  
Cooling  
Changes to Cool when pipe temp is below threshold. Available when SM 171 = 1 or 2  
Pipe Sensor Threshold for 75F to 90F (Default 80F)  
Heating  
Changes to Heat when pipe temp is above threshold. Available when SM 171 = 1 or 2  
Pipe Sensor Purge  
0 = Time (Default)  
1 = Temp  
TEMP: Purge continues until a non-ambiguous condition is sensed.  
TIME: A 3-minute purge is started. Once complete and still ambiguous mode all thermostat  
outputs are disabled for 1 hour.  
Available when SM 171 = 1 or 2  
175  
240  
Fault Detection/ Setback  
0 = Disabled (Default)  
1 = Active On Open  
When enabled connect dry switch between S1 and SC.  
Displays “Door” in clock location, turn outputs OFF, blink red LED  
Displays “Fdd” in clock location, outputs function normally  
Displays “Err” on clock location, turn outputs OFF blink red LED  
Sets thermostat to setback with a closure at SC and S1 .  
(requires SM170=0)  
No remote probe  
2 = Active On Open  
3 = Active On Close  
4 = Occupancy Sensor  
2 or 4 Events (DEFAULT = 2)  
Number of Program  
Events  
When the T8168 is set up as programmable this sets the number of events per day. Events  
are OCC1, UNOCC1, OCC2, UNOCC2  
250  
260  
Clock Format  
F or C  
12 or 24 Hrs (Default = 12)  
0- Celsius  
This service menu sets the clock format.  
Determines temperature displays in Fahrenheit or Celsius  
1- Fahrenheit (Default)  
0-99 Seconds (0-Default)  
270  
280  
Fan Off Delay Heat  
Fan Off Delay Cool  
The amount of time (in seconds) the lowest available fan speed will run after the  
thermostat heating outputs are disabled  
0-99 Seconds (0-Default)  
The amount of time (in seconds) the lowest available fan speed will run after the  
thermostat cooling outputs are disabled  
290  
300  
310  
Range Low  
Range High  
Setback Low  
50-90 F (50F- Default)  
50-90 F (90F Default)  
Off, 50-90 F (67F Default)  
The lowest selectable temperature setpoint value  
The highest selectable temperature setpoint value  
Accessed from Wi-Fi or by occupancy sensor detection.  
“Off” turns heating setpoint off.  
320  
330  
Setback High  
Off, 50-90 F (78F Default)  
+/-9F (0F Default)  
Accessed from Wi-Fi or by occupancy sensor detection.  
“Off” turns cooling setpoint off.  
Zone Temp Offset  
Zone Temperature offset adjusts the sensed Zone Temperature displayed, allowing calibra-  
tion in the field  
© COPYRIGHT 2025 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74599 3220-2406 REV 02  
6
GeneralDetails
NamePECO T8168 Performance Pro Thermostat Installation Guide
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.47 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T372P Thermostat Instruction Manual
PECO T372P Thermostat Instruction Manual
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide
PECO TW180 Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual

PECO T8168 Performance Pro Thermostat Installation Guide