Home > PECO > PECO T8168 Performance Pro Thermostat Installation Guide

PECO T8168 Performance Pro Thermostat Installation Guide

340  
Keypad Lockout  
0- No Key Pad Lockout (Default)  
This function blocks access to certain features of the device. The Service Menu is still avail-  
able if the key pad lockout is enabled.  
1- Disables Schedule and System Keys  
If PIN is entered keypad lockout is overridden for 5 minutes.  
2 - Disables Schedule, System, And Fan  
Keys  
3 - Disables All Keys  
0=Disable, 1= Enable (Default = 0)  
000-999 (Default 000)  
1- On  
341  
342  
350  
Enable Pin Access  
Set Pin  
Applies a 3-digit access code to enter service menu 342  
Selects pin access three-digit code.  
Fan Mode  
ON: Fan is always on, regardless of demand.  
User selections are: ON HI, ON MED, ON LO based on the number of fan speeds.  
2- Auto  
Auto- Fan is only on with heating or cooling demand User selections are: AUTO HI, AUTO  
MED, AUTO LO based on the number of fan speeds.  
3- ON Or Auto (Default)  
4 – Staged Only  
ON or Auto user can choose either selection. User selections are: AUTO HI, AUTO MED,  
AUTO LO, ON HI, ON MED, ON LO based on the number of fan speeds.  
Fan speed selected from available speeds by thermostat per Fan Access section. User selec-  
tions are: AUTO or ON.  
5- On Or Staged - Hotel Mode  
ON- Fan is always on at user selected speed, regardless of demand  
Auto Staged- Fan cycles off with demand. Fan speed is selected by thermostat from avail-  
able fan speeds.  
360  
375  
System Mode  
0- Off, Auto  
Sets the system modes the occupant is able to select  
1- OFF, Heat, Cool, Auto (Default)  
2- OFF, Heat, Cool  
3- Heat, Cool, Auto  
0 = No Flush (Default)  
1 = W1 Flush  
Hotel operation - For ease of use change available System modes to ON-AUTO  
SM360=02  
System Flush Enable  
!
WARNING: Service Menu 375 may disable fan operation during valve flush.  
Enables the flush function for fan coil systems. This feature should be set to 0  
(zero) unless outputs are connected to hydronic heating or cooling valves. Failure to  
follow this instruction can result in damage to equipment and/or property.  
2 = Y1 Flush  
3 = W1 & Y1 Flush  
1 To 3 Minutes (Default 1)  
376  
377  
Flush Duration  
Defines how long to open the valve to perform the flush function  
Flush Frequency  
0 = Every 24 Hrs (Default 0)  
1 = Every 12 Hours  
Defines how often the flush is performed when output has remained inactive  
2 = Every 6 Hours  
380  
390  
395  
Minimum Dead band  
Adjustment  
3F (Default)  
A changeover dead band value prevents short cycling between heating and cooling modes.  
The value is adjustable to meet various HVAC system requirements.  
1-10F, 1.5-5C  
Pre-Occupancy Purge  
0 Hours (Default)  
0-3 Hours  
Energizes the lowest fan available for selected number of hours (0-3) prior to events Occ 1  
and Occ 2. This featrure applies to Programmable thermostat operation.  
Temporary  
Occupied Duration Limit  
0-4 Hours (Default = 3)  
This set the duration of a user override for programmable operation.  
0: Will override the schedule until the next programmed event.  
1,2,3,4: Sets the number of allowed hours of override after user adjustment. User can adjust  
override duration up to this limit of hours.  
480  
500  
Minimum Off Time  
0-10 Minutes (Default 1 Minutes)  
Sets the minimum off time for both the heat and cool output.  
Programmable/  
Intermittent Fan  
0- Disable (Default)  
1 – Programmable Fan  
2 - Intermittent Fan  
In programmable mode the fan will operate continuously during occupied periods or with  
demand during unoccupied/setback periods. In intermittent fan will operate based on the on  
and off times set in menus 501 and 502 whenever there is demand for fan.  
3 - Intermittent Fan During Occupied Periods  
Only  
501  
502  
520  
Intermittent Fan On Time  
Intermittent Fan Off Time  
Default Display Icons  
5 Minutes (Default)  
1-60 Minutes  
Defines the duration in which fan low will be on. Fan On will be activated after Fan Off time  
has passed.  
25 Minutes (Default)  
0-60 Minutes  
Defines the duration in which fan low will be off. Fan Off will be activated after Fan On time  
has passed. A selection of 0 will result in continuous Fan.  
0- Time, Temp, SP (Default)  
1- Time, Temp  
Icons that will be displayed in the default state.  
NOTE: Setpoint will not be displayed if T8168 System Mode is OFF.  
2- Time  
3- Temp  
4- None  
5 - Set Point Only  
Displays Current Revision Information  
530  
Revision  
© COPYRIGHT 2025 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74599 3220-2406 REV 02  
7
GeneralDetails
NamePECO T8168 Performance Pro Thermostat Installation Guide
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.47 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T372P Thermostat Instruction Manual
PECO T372P Thermostat Instruction Manual
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide
PECO TW180 Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual

PECO T8168 Performance Pro Thermostat Installation Guide