Location of the sensor ETS-05
A
B
90°
g
in
ac
r
-T
-E
Heat
-L2
5
ic
on
os
-0
S
tat
r
t
c
T
E
Ele erm
h
T
C
•
•
•
•
•
As indicated in the system design documentation
Away from valves, flanges, supports, pumps, or other heat sinks
At the top of the pipe for thermally sensitive pipe contents (A)
On lower quadrant of pipe 90° for single heating cable (B)
On lower quadrant of pipe centrally between the heating cables if they
are two or more (C)
5
Attachment of the sensor ETS-05
WARNING: Do not install sensor at ambient temperatures below
–20°C. Do not bend sensor (last 50 mm), keep it straight under all
circumstances. Minimum bending radius for High Temperature Mineral
Insulated Sensor extension cable is 20 mm.
20 mm
g
in
ac
r
-T
-E
-L2 Heat
5
ic
-0
S
tat
os
on
r
T
t
E
c
Ele erm
h
T
D
1. Fix sensor firmly on surface with adequate fixing tape in two places (D)
2. Fix sensor parallel to pipe (D)
3. Route extension cable to avoid damage in use. Fix to pipe with
adequate tape where appropriate
8 | nVent.com/RAYCHEM
| General | Details |
|---|---|
| Name | nVent RAYCHEM ETS-05 Electronic Thermostat Instruction Manual |
| Make | nVent RAYCHEM |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.29 MB |

nVent RAYCHEM RAYSTAT-EX-02 Mechanical Thermostat Installation Guide

nVent RAYCHEM Elexant 3500i Electronic Thermostat Installation Guide

nVent RAYCHEM RayStat-M2 Thermostat Instruction Manual

nVent RAYCHEM Green Leaf Programmable Thermostat Instruction Manual

nVent RAYCHEM AT-TS-13 Surface Sensing Thermostat Instruction Manual

nVent RAYCHEM SENZ Wifi Programmable Floor Heating Thermostat User Guide

nVent RAYCHEM GM-TA Thermostat Instruction Manual