nVent RAYCHEM ETS-05 Electronic Thermostat Instruction Manual
8
Testing, commissioning, and maintenance
Test heating cable when thermostat installation is complete as directed
in nVent Installation and Maintenance manual. Maintain thermostat
during normal plant maintenance.
CHECK:
•
•
•
•
•
•
•
•
•
Mounting is firm
Exposed extension cable is not damaged
Gland sealing washer is in place
Gland seal (grommet) is in place
Gland body and nut(s) are tightened firmly
Thermostat operation is correct
Thermostat setting suites application
Lid is closed firmly
Earth wire connecting Earth stud to terminal block Earth is present
and secure
•
Cable type is correct (Insulation >255V and temperature rating to
suit application)
– Note: Cable gland heat-rise could reach 30K
•
Not more than one conductor may be connected into power terminal
block without the use of a single insulated bootlace ferrule
10 | nVent.com/RAYCHEM