Home > neptronic > neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide

neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide

Fan Coil Thermostat  
Specification and Installation Instructions  
Programming mode  
When in this mode this symbol  
is displayed. Please press on button  
to advance to the next program function, press on  
button to return to preceding stage and press on button or to change value. You can leave the programming mode at any  
time, changed values will be recorded.  
Step  
D
i
s
p
l
a
y
Description  
Internal temperature sensor Calibration:  
Values  
Display switches between “tS1” and temperature read by internal  
temperature sensor.  
Range: 10 to 40ºC [50 to 104ºF]  
(max offset 5ºC)  
Increment: 0.1ºC [0.2ºF]  
You can adjust the calibration of the sensor by comparison with a known  
thermometer. For example if thermostat has been installed in an area where  
temperature is slightly different than the room typical temperature  
(thermostat place right under the air diffuser).  
Minimum setpoint:  
Display switches between “Stp” and the minimum setpoint temperature. MIN  
symbol is also displayed.  
Please select the desired minimum setpoint temperature.  
The minimum value is restricted by the maximum value (step #3)  
Maximum setpoint  
Display switches between “Stp” and the maximum setpoint temperature.  
MAX symbol is also displayed.  
Please select the desired maximum setpoint temperature.  
The maximum value is restricted by the minimum value (step #2)  
Locking the setpoint :  
1
Minimum range  
10 to 35ºC [50 to 95ºF]  
Increment: 0.5ºC [1ºF]  
Default value: 15ºC [59ºF]  
2
3
Maximum range  
10 to 35ºC [50 to 95ºF]  
Increment: 0.5ºC [1ºF]  
Default value: 30ºC [86ºF]  
Display switches between “LOC” and “Stp”.  
You can lock or unlock the setpoint adjustment by end user. If locked the  
lock symbol will appear.  
If you do not want to lock setpoint adjustment by end user, go directly to  
step #5.  
Locking the setpoint (cont’d):  
Select the desired locked setpoint temperature; this one should be within  
the temperature range.  
4A  
4B  
5
Default value: Unlocked  
Setpoint range : 10 to 35ºC [50 to 95ºF]  
Increment: 0.5ºC [1ºF]  
Default value: 22ºC [72ºF]  
Adjust the control mode:  
Display switches between “CtL” and “Aut”.  
Select which control mode you want to authorize: Automatic, cooling or  
heating, heating only or cooling only.  
If you want to authorize this entire mode, choose Automatic mode.  
Default value: Cooling only  
Set On/Off function enable or disable:  
Display switches between “OFF” and “ena”.  
You can enable or disable the Automatic mode adjustment by end user.  
Default value: Enable  
6
7
Set 2 pipes or 4 pipes:  
Display switches between “Pno” and “2P”.  
Select which number of pipes you want to use: 2 pipes or 4 pipes.  
If you have selected the 4 pipes, go directly to step #12.  
Default value: 2 pipe  
Change over mode selection:  
Display switches between “COc” and “nc”.  
Please select mode of change over between contact normally cool or  
contact normally heat or external sensor.  
Note: This selection will affect “AO1”  
If normally cool “nc” is selected, heating mode will be activated upon closing  
of contact. If normally heat “nh” is selected, cooling mode will be activated  
upon closing of contact.  
8A  
If external sensor “tS” is selected, heating mode will be activated when  
temperature read by external sensor is above the Change Over SetPoint  
temperature “tCo”, and cooling mode will be activated when temperature  
read by external sensor is under “tCo”, see step #8B.  
If “tS” is not selected, go directly to step #9.  
Default value: Normally cool  
Change over setpoint temperature: (If “tS” has been selected at step #8A)  
Display switches between “tCo” and the change over setpoint temperature  
selected.  
Please select the change over setpoint temperature.  
Note: heating mode will be activated when temperature read by external  
sensor is above the change over setpoint temperature “tCo”, and cooling  
mode will be activated when temperature read by external sensor is under  
“tCo”.  
Range: 10 to 40ºC [50 to 104ºF]  
Increment: 0.5ºC [1ºF]  
Default value: 24ºC [75ºF]  
8B  
8C  
Change over temperature sensor Calibration:  
Display switches between “COs” and the temperature read by the change  
over temperature sensor (if connected).  
You can adjust the calibration of the change over sensor by comparison  
with a known thermometer.  
Range: 10 to 40ºC [50 to 104ºF]  
(max offset 5ºC)  
Increment: 0.1ºC [0.2ºF]  
Display:  
0ºC [32ºF], resistance will be infinite.  
50ºC [122ºF], resistance will be short  
circuited.  
Page | 3  
GeneralDetails
Nameneptronic TFC54F3X1 Fan Coil Thermostat Installation Guide
Makeneptronic
LanguageEnglish
FiletypePDF (Download)
File size0.5 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
neptronic STS3 Series Wall Thermostat Instruction Manual
neptronic STS3 Series Wall Thermostat Instruction Manual
neptronic ITO3-C Wall Thermostat Owner’s Manual
neptronic ITO3-C Wall Thermostat Owner’s Manual
neptronic TMA54-EXT1 Thermostat Instruction Manual
neptronic TMA54-EXT1 Thermostat Instruction Manual

neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide