neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide

Fan Coil Thermostat  
Specification and Installation Instructions  
Step  
Display  
Description  
Set local reheat On/Off or TPM: (If you have selected 2pipe control mode at step #7)  
Values  
Display switches between “LHt” and “OFF”.  
Select which signal output you want for AO2. You can choose OFF (no  
signal selected), ON analog heating only, ON analog heating & fan output.  
9
Default value: Off  
Proportional band range:  
If you select OFF (no local reheat), go directly to step #14.  
Proportional band for local reheat (AO2):  
Display switches between “Pb.L” and the value of the local reheat  
proportional band, heating symbol is also displayed.  
Please select the desired value of local reheat proportional band.  
0.5 to 5.0ºC [1.0 to 10.0ºF]  
Increment: 0.5ºC [1.0ºF]  
Default value: 2.0ºC [4.0ºF]  
10  
11  
12  
Dead band for local reheat (AO2):  
Proportional band range:  
0.3 to 5.0ºC [0.6 to 10.0ºF]  
Increment: 0.1ºC [0.2ºF]  
Default value: 0.3ºC [0.6ºF]  
Display switches between “db. L” and the value of the local reheat dead  
band, heating symbols are also displayed.  
Please select the desired value of local reheat dead band.  
Go to step #14.  
Internal/external temperature sensor selection:  
Display switches between “tS” and “in” or “out.  
Please select internal or external sensor.  
Default value: Internal  
temperature sensor  
External temperature sensor Calibration:  
Display switches between “tS2” and the temperature read by the external  
temperature sensor (if connected).  
You can adjust the calibration of the external sensor by comparison with a  
known thermometer.  
Range: 10 to 40ºC [50 to 104ºF]  
(max offset 5ºC)  
Increment: 0.1ºC [0.2ºF]  
Display:  
0ºC [32ºF], resistance will be infinite.  
50ºC [122ºF], resistance will be short  
circuited.  
13  
Proportional band 1 in heating:  
Proportional band range:  
0.5 to 5.0ºC [1.0 to 10.0ºF]  
Increment: 0.5ºC [1.0ºF]  
Default value: 2.0ºC [4.0ºF]  
Display switches between “Pb.1” and the value of the 1st heating  
proportional band, heating symbol is also displayed.  
Please select the desired value of 1st heating proportional band.  
14  
15  
16  
17  
Proportional band 1 in cooling:  
Proportional band range:  
0.5 to 5.0ºC [1.0 to 10.0ºF]  
Increment: 0.5ºC [1.0ºF]  
Default value: 2.0ºC [4.0ºF]  
Display switches between “Pb.1” and the value of the 1st cooling  
proportional band, cooling symbol is also displayed.  
Please select the desired value of 1st cooling proportional band.  
Dead band in heating:  
Proportional band range :  
0.3 to 5.0ºC [0.6 to 10.0ºF]  
Increment: 0.1ºC [0.2ºF]  
Default value: 0.3ºC [0.6ºF]  
Display switches between “db.1” and the value of the dead band in heating,  
heating symbols are also displayed.  
Please select the desired value of dead band in heating.  
Dead band in cooling:  
Proportional band range :  
0.3 to 5.0ºC [0.6 to 10.0ºF]  
Increment: 0.1ºC [0.2ºF]  
Default value: 0.3ºC [0.6ºF]  
Display switches between “db.1” and the value of the dead band in cooling,  
cooling symbols are also displayed.  
Please select the desired value of dead band in cooling.  
Minimum position of Ao1 ramp:  
Display switches between “Ao.1and the value of the minimum position of  
the Ao1 ramp. MIN symbol is also displayed.  
Please select the desired value of the minimum position of the Ao1 ramp.  
Range: 0.0 to 10.0 Volt.  
Increment: 0.2 Volt.  
Default value: 0.0 Volt  
18  
19  
20  
(This is the “zero” value)  
The minimum value is restricted by the maximum value. (step #19)  
Maximum position of Ao1 ramp:  
Display switches between “Ao.1and the value of the maximum position of  
the Ao1 ramp. MAX symbol is also displayed.  
Please select the desired value of the minimum position of the Ao1 ramp.  
Range: 0.0 to 10.0 Volt.  
Increment: 0.1 Volt.  
Default value: 10.0 Volt  
(This is the “span” value)  
The maximum value is restricted by the minimum value. (step #18)  
Minimum position of Ao2 ramp:  
Display switches between “Ao.2and the value of the minimum position of  
the Ao2 ramp. MIN symbol is also displayed.  
Please select the desired value of the minimum position of the Ao2 ramp.  
Range: 0.0 to 10.0 Volt.  
Increment: 0.2 Volt.  
Default value: 0.0 Volt  
(This is the “zero” value)  
The minimum value is restricted by the maximum value. (step #21)  
Maximum position of Ao2 ramp:  
Display switches between “Ao.2and the value of the maximum position of  
the Ao2 ramp. MAX symbol is also displayed.  
Please select the desired value of the minimum position of the Ao2 ramp.  
Range: 0.0 to 10.0 Volt.  
Increment: 0.1 Volt.  
Default value: 10.0 Volt  
21  
22  
(This is the “span” value)  
The maximum value is restricted by the minimum value. (step #20)  
Set fan speed automatic mode enable or disable:  
Display switches between “FAn” and “ena”. Fan symbol is also displayed.  
You can enable or disable the Automatic mode adjustment by end user.  
If you selected to disable the automatic mode, go directly to step #24  
Default value: Enable  
Page | 4  
GeneralDetails
Nameneptronic TFC54F3X1 Fan Coil Thermostat Installation Guide
Makeneptronic
LanguageEnglish
FiletypePDF (Download)
File size0.5 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
neptronic STS3 Series Wall Thermostat Instruction Manual
neptronic STS3 Series Wall Thermostat Instruction Manual
neptronic ITO3-C Wall Thermostat Owner’s Manual
neptronic ITO3-C Wall Thermostat Owner’s Manual
neptronic TMA54-EXT1 Thermostat Instruction Manual
neptronic TMA54-EXT1 Thermostat Instruction Manual

neptronic TFC54F3X1 Fan Coil Thermostat Installation Guide