Home > MClimate > MClimate MC-LW-FCT-01 LoRaWAN Fan Coil Thermostat User Manual

MClimate MC-LW-FCT-01 LoRaWAN Fan Coil Thermostat User Manual

Technical specifications  
Designed and manufactured by MClimate™ in the EU.  
SKU: MC-LW-FCT-01  
Dimensions: 105 x 115 x 23mm  
Weight: 220gr  
Legal Notices  
All information, including but not limited to,  
Based on EU Regulation 813/2013(Eco design directive) and  
811/2013 (Labeling directive) concerning space heaters,  
combination heaters ,the following classes apply:  
Application with On / Off operation of a heater Class I value  
1.0% PWM (TPI) room thermostat, for use with Class IV value  
2.0% On/Off output heaters RDG110 Application with On /  
Off operation of a heater Class I value 1.0% RDG100../RDG110  
features, functionality, and  
/
or other product  
specifications are subject to change without notice.  
MClimate retains all rights to review or update its  
products, software or documentation without being  
required to notify any natural or legal person.  
Materials: ABS, PC, Stainless steel  
Radio frequency range: 863÷870MHz / 902-928MHz  
Radio technology: LoRaWAN Class C, EU868, US915, AS923 and AU915  
Power supply: 110-240VAC, 50/60Hz, 5mA  
The MClimate and MClimate logo are trademarks of  
MClimate Jsc. All other brands and product names  
mentioned herein are trademarks of their  
respective owners.  
Sensors: Temperature & Humidity  
Operating conditions:  
Operating temperature: 0°С to +50°С  
Operating humidity: 0-80% RH (non-condensing)  
Storage & Transport conditions: As per IEC 60721-3-1  
Temperature: −25…65 °C  
Humidity: <95% r.h.  
IP rating: IP31 (EN60529)  
Mounting options: Screws and dowels on a wall or screws  
only on an electrical box; Anti-theft bracket with secure  
screw (T5 Torx).  
Outputs:  
Output (1-4): 5(2)A  
Output 5NA, 5NC: 5A  
No internal fuse. External preliminary protection with max. current  
10A circuit breaker required in all cases.  
EU Declaration of Conformity  
This device complies with the essential  
requirements and other applicable provisions of  
the following EU directives:  
Fan Control (1-3 speed fans): Q1, Q2, Q3 - 220VAC  
Rating min, max, resistive (inductive): 5(2)A  
Fan Control (ECM fans): IO1 and IO2, control signal between 0VDC and  
10VDC  
2014/53/EC  
EN IEC 60730-2-9  
EN IEC 62368-1  
EN 55032  
Fans must NOT be connected in parallel! Connect one fan directly, for  
additional fans, one relay for each speed.  
EN 55035  
Safety Instructions  
Environmental conditions in which the device is intended to  
operate:  
Control outputs V1: V1-V4: 230V AC; 5A resistive load, 2A (cos > 0,4)  
Control output V2: 230V AC, resistive load only, max 5A  
3A fast microfuse, cannot be exchanged  
- Indoor use only;  
- for altitude up to 2000m;  
Multifunctional analogue/digital input/output IO1 and IO2:  
Operation: Selectable through downlink. Available options are auto  
change-over NTC, ECM FAN, filter alarm contact, dew point sensor  
contact, occupancy (keycard) contact.  
- for an ambient temperature: 0°С to +50°С;  
- for maximum relative humidity of 80% for temperature up  
to 31°С, decreasing  
linearly to 25% relative humidity at temperature 50°С;  
- for an environment with a degree of contamination 2  
(PD2).  
Change-Over temperature sensor:  
Type: 10k NTC (10k at 25 degrees C)  
Temperature range: 0 to 125 degrees C  
Maximum cable length: 50m at 1.5mm2 (AWG 16).  
Connection terminals: Solid wire or prepared stranded wire, 0.25mm2 -  
1.5mm2 (AWG 24 to AWG 16)  
4
GeneralDetails
NameMClimate MC-LW-FCT-01 LoRaWAN Fan Coil Thermostat User Manual
MakeMClimate
LanguageEnglish
FiletypePDF (Download)
File size3.74 MB
Download PDF