Home > iO HVAC Controls > iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual

iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual

2
HEAT / 1 COOL DUAL FUEL  
TYPICAL SYSTEM WIRING DIAGRAMS  
2 HEAT / 1 COOL HEAT PUMP  
Y2  
G2  
W1  
O/B  
W2  
G3  
G1  
R
24  
24C  
B
A
T
T
Y1  
TERMINALS  
AUX  
HEAT  
REV  
VALVE  
FAN 1  
RELAY  
TT  
MODBUS  
TERMINALS  
COMP 1  
RELAY  
Switch Settings  
24 V  
LINE  
Sw1 = OFF  
Sw2 = ON  
Sw3 = OFF  
(Fan Relay)  
(Heat Pump)  
(Single Stage)  
Switch Settings  
Sw1 = OFF  
Sw2 = ON  
Sw3 = OFF  
(Fan Relay)  
(Heat Pump)  
(Single Stage)  
Sw4 = Reversing Valve  
(OFF = ‘O’ - RV Energized in Cooling)  
(ON = ‘B’ - RV Energized in Heating)  
Sw5 = Installer Preference  
(OFF = No Short Cycle Protection)  
(ON = 4 Minute Short Cycle Protection)  
Sw6 = User Preference  
(OFF = Non-programmable)  
(ON = Programmable)  
Sw7 = Installer Preference  
Sw4 = Reversing Valve  
(OFF = ‘O’ - RV Energized in Cooling)  
(ON = ‘B’ - RV Energized in Heating)  
Sw5 = Installer Preference  
(OFF = No Short Cycle Protection)  
(ON = 4 Minute Short Cycle Protection)  
Sw6 = User Preference  
(OFF = Non-programmable)  
(ON = Programmable)  
Sw7 = Installer Preference  
(OFF = 2 Minute Minimum Run Time)  
(ON = 6 Minute Minimum Run Time)  
Sw8 = ON  
(OFF = 2 Minute Minimum Run Time)  
(ON = 6 Minute Minimum Run Time)  
Sw8 = ON  
(Separate Heating and Cooling Setpoints)  
3
HEAT / 2 COOL DUAL FUEL  
(Separate Heating and Cooling Setpoints)  
3 HEAT / 2 COOL HEAT PUMP  
FOSSIL  
REV  
FAN 1  
TERMINALS  
Y2  
G2  
W2  
G3  
W1  
O/B  
G1  
R
24  
24C  
B
A
T
T
Y1  
COMP 2  
COMP 1  
AUX  
HEAT  
REV  
VALVE  
FAN 1  
RELAY  
TT  
MODBUS  
TERMINALS  
Switch Settings  
COMP 2  
RELAY  
COMP 1  
RELAY  
LINE  
24 V  
(Separate Heating and Cooling Setpoints)  
Switch Settings  
Sw1 = OFF  
(Fan Relay)  
Sw2 = ON  
Sw3 = ON  
Sw4 = Reversing Valve  
(Heat Pump)  
(Two Stage)  
Sw1 = OFF  
Sw2 = ON  
Sw3 = ON  
(Fan Relay)  
(Heat Pump)  
(Two Stage)  
(OFF = ‘O’ - RV Energized in Cooling)  
(ON = ‘B’ - RV Energized in Heating)  
Sw5 = Installer Preference  
(OFF = No Short Cycle Protection)  
(ON = 4 Minute Short Cycle Protection)  
Sw6 = User Preference  
Sw4 = (Reversing Valve)  
(OFF = ‘O’ - RV Energized in Cooling)  
(ON = ‘B’ - RV Energized in Heating)  
Sw5 = Installer Preference  
(OFF = No Short Cycle Protection)  
(ON = 4 Minute Short Cycle Protection)  
Sw6 = User Preference  
(OFF = Non-programmable)  
(ON = Programmable)  
Sw7 = Installer Preference  
(OFF = Non-programmable)  
(ON = Programmable)  
(OFF = 2 Minute Minimum Run Time)  
(ON = 6 Minute Minimum Run Time)  
Sw8 = ON  
Sw7 = Installer Preference  
(Off = 2 Minute Minimum Run Time)  
(ON = 6 Minute Minimum Run Time)  
Sw8 = ON  
(Separate Heating and Cooling Setpoints)  
5
GeneralDetails
NameiO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual
MakeiO HVAC Controls
LanguageEnglish
FiletypePDF (Download)
File size0.36 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual
iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual
iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual
iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual

iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual