Home > iO HVAC Controls > iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual
iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual
2
HEAT / 1 COOL DUAL FUEL
TYPICAL SYSTEM WIRING DIAGRAMS
2 HEAT / 1 COOL HEAT PUMP
Y2
G2
W1
O/B
W2
G3
G1
R
24
24C
B
A
T
T
Y1
TERMINALS
AUX
HEAT
REV
VALVE
FAN 1
RELAY
TT
MODBUS
TERMINALS
COMP 1
RELAY
Switch Settings
24 V
LINE
Sw1 = OFF
Sw2 = ON
Sw3 = OFF
(Fan Relay)
(Heat Pump)
(Single Stage)
Switch Settings
Sw1 = OFF
Sw2 = ON
Sw3 = OFF
(Fan Relay)
(Heat Pump)
(Single Stage)
Sw4 = Reversing Valve
(OFF = ‘O’ - RV Energized in Cooling)
(ON = ‘B’ - RV Energized in Heating)
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
(OFF = Non-programmable)
(ON = Programmable)
Sw7 = Installer Preference
Sw4 = Reversing Valve
(OFF = ‘O’ - RV Energized in Cooling)
(ON = ‘B’ - RV Energized in Heating)
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
(OFF = Non-programmable)
(ON = Programmable)
Sw7 = Installer Preference
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
(Separate Heating and Cooling Setpoints)
3
HEAT / 2 COOL DUAL FUEL
(Separate Heating and Cooling Setpoints)
3 HEAT / 2 COOL HEAT PUMP
FOSSIL
REV
FAN 1
TERMINALS
Y2
G2
W2
G3
W1
O/B
G1
R
24
24C
B
A
T
T
Y1
COMP 2
COMP 1
AUX
HEAT
REV
VALVE
FAN 1
RELAY
TT
MODBUS
TERMINALS
Switch Settings
COMP 2
RELAY
COMP 1
RELAY
LINE
24 V
(Separate Heating and Cooling Setpoints)
Switch Settings
Sw1 = OFF
(Fan Relay)
Sw2 = ON
Sw3 = ON
Sw4 = Reversing Valve
(Heat Pump)
(Two Stage)
Sw1 = OFF
Sw2 = ON
Sw3 = ON
(Fan Relay)
(Heat Pump)
(Two Stage)
(OFF = ‘O’ - RV Energized in Cooling)
(ON = ‘B’ - RV Energized in Heating)
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
Sw4 = (Reversing Valve)
(OFF = ‘O’ - RV Energized in Cooling)
(ON = ‘B’ - RV Energized in Heating)
Sw5 = Installer Preference
(OFF = No Short Cycle Protection)
(ON = 4 Minute Short Cycle Protection)
Sw6 = User Preference
(OFF = Non-programmable)
(ON = Programmable)
Sw7 = Installer Preference
(OFF = Non-programmable)
(ON = Programmable)
(OFF = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
Sw7 = Installer Preference
(Off = 2 Minute Minimum Run Time)
(ON = 6 Minute Minimum Run Time)
Sw8 = ON
(Separate Heating and Cooling Setpoints)
5
| General | Details |
|---|---|
| Name | iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual |
| Make | iO HVAC Controls |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.36 MB |

iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual

iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual