Confirm the resistance value (within 5%) to the
temperature where the sensor is mounted.
Disconnect power to the thermostat when wiring
the sensor to the ‘T’ and ‘T’ terminals. Strip only as
much insulation off of the wires as necessary to
provide a good contact with the terminals. The
sensor is not polarity specific so either sensor lead
may be connected to either terminal on the
BASIC TROUBLE SHOOTING
POSSIBLE FAULT AND REMEDY
SYMPTOM
Wrench icon flashes
on LCD
This is not a fault. Commissioning mode is
enabled and time delays are overridden.
Change CD=1 to CD=0 in the Advanced
Outdoor temperature
does not display.
Dashes (---) appear
on the LCD.
Check wiring to outdoor sensor. Make sure
that TT=OA in the Advanced Installer menu.
OUTDOOR SENSOR INSTALLATION
This is not a fault. The T-32-P2 has a built-in
minimum equipment run time of either 2 or 6
minutes. Sw6 may set for 6 minutes (ON)
which is keeping the equipment on after the
thermostat reaches setpoint. Try setting
Heating or Cooling is
flashing while the
HVAC system is
running.
Mount the sensor on a vertical exterior surface
below an overhang. Choose a location protected
from direct sunlight and exposure to excessive
moisture. Follow the same wiring and test
procedures as installing an indoor sensor.
Lock icon flashes
when trying to set a
higher heating or
lower cooling
This is not a fault. HL and CL restrict the
heating and cooling setpoints. The limit
values can be changed in the Advanced
Installer menu.
SENSOR CALIBRATION CHART
temperature.
Temperature
Resistance
Temperature
Resistance
The T-32-P2 can display in either
Fahrenheit or Celsius. Change CF=C or F
in the Advanced Installer menu.
Thermostat
displays wrong
temperature.
(°F)
(kΩ)
(°F)
(kΩ)
34.6
26.1
19.9
15.3
30
40
50
60
70
11.9
9.4
80
The thermostat is set to Fan ON. Set the
thermostat to Auto Fan. The fan purge
mode is set to run the fan for a fixed period
of time after the equipment shuts off.
Change the FP value in the Advanced
Installer menu.
The fan continues
to run after a
heating or cooling
call is satisfied.
90
7.4
100
5.9
Lock values have been set. Refer to LC
settings in the Advance Installer menu.
Some buttons on
the thermostat do
not function.
SPECIFICATIONS
Input Voltage
Relay Rating
24 VAC 50/60 Hz
24 VAC @ 1Amp maximum
per relay
32° F to 122° F
0-95% (non-condensing)
32° F to 105° F
Make sure that the plastic tab on the
internal fitted battery is removed so that the
battery is operational.
Thermostat clock
does not keep
proper time.
Operating Temperature
Operating RH
Storage Temperature
Size
4-7/16” W x 4-1/16” H x 7/8” D
2-3/4” W x 1-7/8” H
10K NTC type 2
20-30 VAC
10kΩ @ 77° F
+/- 3% @ 77° F
Minimum temperature change
over time
5 - 90 minutes
Off to 4 minutes
0.1° F
LCD Display Size
Temperature Sensor
Voltage
Resistance
Tolerance
REMOTE SENSOR INSTALLATION INSTRUCTIONS
The T-32-P2 can use an indoor remote sensor or
multiple sensors for temperature averaging or as
an outdoor sensor for temperature display or a
control function depending upon the thermostat
configuration.
Stage Delays
Timed Upstage Delay
Short-cycle Delay
Display Resolution
Control Range
Outdoor Air Temperature Range
Back Light
Optimized Start/Stop Method
Off to 105° F
-10° F to 140° F
Blue EL (Electro Luminescent)
Time to start vs. temperature
differential
Modbus
FCC (Part 15) (Pending)
5 years
INDOOR SENSOR INSTALLATION
Locate the sensor in the same manner as a
thermostat. Mount the sensor 18” away from any
outside wall. Do not install the sensor behind
doors, in corners or other dead air spaces. Keep
the sensor away from direct air flow, supply
registers or near sources of heat such as lamps
and appliances. The maximum wire length from the
sensor to the thermostat is 300 feet. Use a
separate 18-2 thermostat cable for sensor wiring.
Prior to wiring the sensor to the thermostat, use an
ohm-meter or multimeter to measure the
Communications Protocol
Approvals
Warranty
The T-32-P2 can be configured for 3-speed fan and
single setpoint control.
For information regarding these features, contact
iO HVAC Controls at 888-359-0362
resistance of the sensor. Measure at the end of the
wires that will connect to the thermostat.
iO-06-1414-012225
11
| General | Details |
|---|---|
| Name | iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual |
| Make | iO HVAC Controls |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.36 MB |

iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual

iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual