Confirm the resistance value (within 5%) to the  
temperature where the sensor is mounted.  
Disconnect power to the thermostat when wiring  
the sensor to the ‘T’ and ‘T’ terminals. Strip only as  
much insulation off of the wires as necessary to  
provide a good contact with the terminals. The  
sensor is not polarity specific so either sensor lead  
may be connected to either terminal on the  
BASIC TROUBLE SHOOTING  
POSSIBLE FAULT AND REMEDY  
SYMPTOM  
Wrench icon flashes  
on LCD  
This is not a fault. Commissioning mode is  
enabled and time delays are overridden.  
Change CD=1 to CD=0 in the Advanced  
Outdoor temperature  
does not display.  
Dashes (---) appear  
on the LCD.  
Check wiring to outdoor sensor. Make sure  
that TT=OA in the Advanced Installer menu.  
OUTDOOR SENSOR INSTALLATION  
This is not a fault. The T-32-P2 has a built-in  
minimum equipment run time of either 2 or 6  
minutes. Sw6 may set for 6 minutes (ON)  
which is keeping the equipment on after the  
thermostat reaches setpoint. Try setting  
Heating or Cooling is  
flashing while the  
HVAC system is  
running.  
Mount the sensor on a vertical exterior surface  
below an overhang. Choose a location protected  
from direct sunlight and exposure to excessive  
moisture. Follow the same wiring and test  
procedures as installing an indoor sensor.  
Lock icon flashes  
when trying to set a  
higher heating or  
lower cooling  
This is not a fault. HL and CL restrict the  
heating and cooling setpoints. The limit  
values can be changed in the Advanced  
Installer menu.  
SENSOR CALIBRATION CHART  
temperature.  
Temperature  
Resistance  
Temperature  
Resistance  
The T-32-P2 can display in either  
Fahrenheit or Celsius. Change CF=C or F  
in the Advanced Installer menu.  
Thermostat  
displays wrong  
temperature.  
(°F)  
(kΩ)  
(°F)  
(kΩ)  
34.6  
26.1  
19.9  
15.3  
30  
40  
50  
60  
70  
11.9  
9.4  
80  
The thermostat is set to Fan ON. Set the  
thermostat to Auto Fan. The fan purge  
mode is set to run the fan for a fixed period  
of time after the equipment shuts off.  
Change the FP value in the Advanced  
Installer menu.  
The fan continues  
to run after a  
heating or cooling  
call is satisfied.  
90  
7.4  
100  
5.9  
Lock values have been set. Refer to LC  
settings in the Advance Installer menu.  
Some buttons on  
the thermostat do  
not function.  
SPECIFICATIONS  
Input Voltage  
Relay Rating  
24 VAC 50/60 Hz  
24 VAC @ 1Amp maximum  
per relay  
32° F to 122° F  
0-95% (non-condensing)  
32° F to 105° F  
Make sure that the plastic tab on the  
internal fitted battery is removed so that the  
battery is operational.  
Thermostat clock  
does not keep  
proper time.  
Operating Temperature  
Operating RH  
Storage Temperature  
Size  
4-7/16” W x 4-1/16” H x 7/8” D  
2-3/4” W x 1-7/8” H  
10K NTC type 2  
20-30 VAC  
10kΩ @ 77° F  
+/- 3% @ 77° F  
Minimum temperature change  
over time  
5 - 90 minutes  
Off to 4 minutes  
0.1° F  
LCD Display Size  
Temperature Sensor  
Voltage  
Resistance  
Tolerance  
REMOTE SENSOR INSTALLATION INSTRUCTIONS  
The T-32-P2 can use an indoor remote sensor or  
multiple sensors for temperature averaging or as  
an outdoor sensor for temperature display or a  
control function depending upon the thermostat  
configuration.  
Stage Delays  
Timed Upstage Delay  
Short-cycle Delay  
Display Resolution  
Control Range  
Outdoor Air Temperature Range  
Back Light  
Optimized Start/Stop Method  
Off to 105° F  
-10° F to 140° F  
Blue EL (Electro Luminescent)  
Time to start vs. temperature  
differential  
Modbus  
FCC (Part 15) (Pending)  
5 years  
INDOOR SENSOR INSTALLATION  
Locate the sensor in the same manner as a  
thermostat. Mount the sensor 18” away from any  
outside wall. Do not install the sensor behind  
doors, in corners or other dead air spaces. Keep  
the sensor away from direct air flow, supply  
registers or near sources of heat such as lamps  
and appliances. The maximum wire length from the  
sensor to the thermostat is 300 feet. Use a  
separate 18-2 thermostat cable for sensor wiring.  
Prior to wiring the sensor to the thermostat, use an  
ohm-meter or multimeter to measure the  
Communications Protocol  
Approvals  
Warranty  
The T-32-P2 can be configured for 3-speed fan and  
single setpoint control.  
For information regarding these features, contact  
iO HVAC Controls at 888-359-0362  
resistance of the sensor. Measure at the end of the  
wires that will connect to the thermostat.  
iO-06-1414-012225  
11  
GeneralDetails
NameiO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual
MakeiO HVAC Controls
LanguageEnglish
FiletypePDF (Download)
File size0.36 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual
iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual
iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual
iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual

iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual