Home > iO HVAC Controls > iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual
iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual
ENTERING THE ADVANCED INSTALLER SETTINGS MENU
ADVANCED INSTALLER SETTINGS MENU
The T-32-P2 contains factory defaults for all Advanced
Installer Settings. Depending upon the user and
equipment application, some settings may need to be
changed.
Symbol Default
Function
ST S8
OF
Leave at factory default
SC SC
OF
Leave at factory default
To enter the Advanced Installer Settings menu, push the
O/RIDE button once then hold it down (15 seconds) until
the number “88:15” is displayed on the LCD. Using the
( ) ( ) arrow button, adjust the value until it reads
“88:32” and then press the O/RIDE button to enter the
menu. You can move forward or backwards through the
menu by pressing the O/RIDE or PROG buttons.
FO=2 - In programmable mode
(Sw6=ON), fan runs continuously with
program 1 through 4 and then in AUTO
from program 4 - 1.
ADVANCED INSTALLER SETTINGS MENU
FO=3 - In programmable mode
(Sw6=ON), fan control is a combination
of option 1 and 2.
Symbol Default
Function
PN 88
32
Keyboard Lock PIN. This is the required
PIN for future entry into the Advanced
Installer Setup menu. (Range 00-99)
Fan Purge
FP FP
0
Adjustable from 0 - 5 minutes after
heating or cooling cycle.
LC LC
00
Keyboard Lock OFF
FN 88
A
Mode - Heat / Cool system.
Programmable Mode
LC=01 - All buttons are locked except
( ) ( ) buttons.
LC=02 - All buttons are locked except
O/RIDE and( ) ( ) buttons.
FN=C - Cooling only system.
FN=H - Heating only system.
LC=03 - All buttons are locked except
MODE, O/RIDE and ( ) ( ) buttons.
LC=04 - All buttons are locked except
H3 H3
AL
H3=AL - W2 relay used for auxiliary and
emergency heat.
(Sw1 = OFF) (Sw2 = ON)
MODE and ( ) ( ) buttons.
LC=05 - All buttons are locked except
O/RIDE button.
H3=EH - W2 relay controls emergency
heat.
H3=AH - Do not use this function.
H3=FF - Fossil Fuel (Y is locked out
when W2 is energized.
H3 = OF - W2 relay only operates as
auxiliary heat in heat pump mode.
LC=06 - All buttons are locked.
LC=00 - Keyboard lock OFF.
LC=01 - All buttons are locked except
MODE button.
LC=02 - All buttons are locked except
MODE and ( ) ( ) buttons.
LC=03 - FAN, and PROG are locked.
MODE button can only select Auto or
Manual Mode
(Sw6=OFF)
For NO remote sensor OR 1 or more
remote indoor sensor without the
onboard sensor being used.
TT 88
RS
OFF.
TT=OA - For outdoor remote sensor
connection.
LC-04 - MODE button can only select
Auto or OFF.
LC-05 - All buttons are locked.
LC-06 - Same function as LC-05.
TT=DA - Sends measured temperature
from remote sensor via modbus but
does not display the value on the LCD.
TT=OC - For connecting dry contact
switch.
HL HL
90
50
Maximum Heating or High Temperature
Limit.(Adjustable from 41° F - 120° F)
(Replaces user setpoints with
pre-programmed cooling ‘OC’ and
heating ‘OH’ setpoints)
CL CL
Minimum Cooling or Low Temperature
Limit. (Adjustable from 43° F - 122° F)
TT=OF - For connecting dry contact
switch.
CF CF
F
Temperature Display
(Degrees F or C)
(Turns thermostat off when closed)
TT=AV - For averaging BOTH the
C1 CI
0.0
Internal Sensor Calibration
(Adjustable +/- 9° F)
sensor and remote
internal thermostat
indoor sensor(s) together.
AF AF
1
Freeze protection ON. If thermostat is
OFF, heating will come on if room
temperature falls below 41° F.
Time Format
(12 or 24 Hour Clock)
TC 8C
12
0
TD 88
Temperature Display
AF=0 - No freeze protection.
TD=0 - Displays set and space
temperatures.
TD=1 - Displays only the set
OH 8H
OF
OF
Override Heating Setpoint.
(Adjustable from 41° F - 120° F)
temperature.
AH AH
2.0
After Hours Override Timer
OC 8C
Override Cooling Setpoint.
(Adjustable from 43° F - 122° F)
Temporary Program Override 0 (OFF)
extends override to next program
change. 1 - 12 equals fixed hours of
override.
4 Schedules
(Sw6=ON)
(Sw8=ON)
7
| General | Details |
|---|---|
| Name | iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual |
| Make | iO HVAC Controls |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.36 MB |