ADVANCED INSTALLER SETTINGS MENU  
ADVANCED INSTALLER SETTINGS MENU  
Symbol Default  
Function  
Symbol Default  
Function  
Start/Stop Mode.  
(Controlled by thermostat program)  
SS SS  
0
SP SP  
SD S8  
S3 S3  
1
1
1.4° F differential for stage 1.  
SP=2 - 1.9° F differential.  
SP=3 - 2.4° F differential.  
SS=1 - Thermostat in Start only mode  
per call by Modbus Master.  
SS=2 - Thermostat in Stop only mode  
per call by Modbus Master.  
1.4° F differential for stage 2.  
SP=2 - 1.9° F differential.  
SP=3 - 2.4° F differential.  
OF 08  
0
Leave at factory default  
Response Time.  
(Leave at factory default)  
RS 8S  
50  
1
1.4° F differential for stage 3.  
TS 8S  
0
Factory Test Mode OFF.  
S3=2 - 1.9° F differential.  
S3=3 - 2.4° F differential.  
TS=1 - Display configuration code.  
TS=2 - Step cycle all relays in  
sequence.  
TS=3 - Reset software to factory  
defaults.  
SU su  
10  
20  
Leave at factory default.  
Upstage Timer.  
DT 88  
(Adjustable from 10 - 90 minutes in  
5 minute increments) Only works if  
thermostat has not called for 2nd or  
3rd stage. (Sw3=ON)  
(Press fan button to initiate)  
TT TERMINAL FUNCTIONS  
OS 8S  
1
Adaptive Recovery ON.  
OS-0 = Adaptive Recovery OFF.  
The ‘T’ and ‘T’ terminals on the T-32-P2 are primarily  
used for wiring either an indoor or an outdoor remote  
sensor. The terminals are not polarity dependent. The  
terminals can also be used for other functions such as  
remote ON/OFF switching of various control functions  
depending upon thermostat configuration. Each  
configuration requires setup in the Advanced Installer  
menu.  
C2 C2  
0.0  
55  
Remote sensor calibration.  
(Adjustable +/- 9° F)  
CO C8  
Cooling OFF temperature. Only  
works if TT-OA with outdoor sensor.  
When outdoor temperature falls below  
setpoint, cooling will shut off.  
(Adjustable from 41° F - 122°F)  
HO H8  
75  
Heating OFF temperature. Only works if  
TT=OA with outdoor sensor. When  
outdoor temperature rises above  
setpoint, heating will shut off.  
REMOTE SENSORS  
There are two type of remote sensors. The T-32-S1 is  
a single sensor that can be used indoors or outdoors.  
The T-32-S2 contains two sensors. A combination of  
both sensors can be used for indoor temperature  
averaging to simplify wiring.  
(Adjustable from 41° F - 122° F)  
HB H8  
55  
35  
High Balance Point.  
Only works if TT=OA with outdoor  
sensor and H3=FF  
for fossil fuel. W2 auxiliary heat  
is locked out when temperature rises  
above HB setpoint.  
OUTDOOR SENSOR WIRING  
(Adjustable from 32° F - 122° F)  
When the T-32-S1 is used as an outdoor sensor, the  
T-32-P2 will display the outside air temperature. In  
the  
LB L8  
Low Balance Point.  
Only works if TT=OA with outdoor  
sensor and H3=FF  
for fossil fuel. W2 auxiliary heat is  
locked out when temperature falls  
below LB setpoint.  
Advanced Installer menu, TT=OA. The outdoor sensor  
can also be used for high and low balance point  
control in dual fuel systems. Use separate 18-2  
thermostat cable when wiring the sensor to the  
thermostat. If the outdoor sensor fails, or is not wired  
properly, two dashes will appear on the LCD where  
the outside temperature would normally be displayed.  
(Figure 6)  
(Adjustable from 15° F - 77° F)  
FT 88  
OF  
1
Replace or clean filter.  
(Off to 900 hours in 100 hour  
increments)  
AD A8  
Modbus Address.  
(Adjustable from 0 to 32)  
Y2  
G2  
W1  
O/B  
W2  
G3  
24  
24C  
B
A
T
T
G1  
R
Y1  
BD 88  
19.2  
Baud Rate.  
T-32-S1 SENSOR  
BD=4.8  
BD=9.6  
CD C8  
0
Commissioning Mode  
OFF.  
(All time delays active)  
CD=1- Commissioning  
Mode ON.  
(All time delays inactive)  
FIGURE 6  
8
GeneralDetails
NameiO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual
MakeiO HVAC Controls
LanguageEnglish
FiletypePDF (Download)
File size0.36 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual
iO HVAC Controls UT32 Titan 3H or 2C Touchscreen Thermostat Owner’s Manual
iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual
iO HVAC CONTROLS Z-2000-T Thermostat Instruction Manual

iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual