SYSTEM SWITCH FUNCTIONS
SPECIAL INSTRUCTIONS FOR DUAL FUEL APPLICATIONS
Sw1 - Fan Relay
Sw2 - Equipment
Leave Switch 1 OFF
(factory default).
When the T-32-P2 is used with dual fuel systems,
an outdoor sensor is recommended for balance
point control (Model T-32-S1). The sensor is wired
to the TT terminals on the thermostat. In the
Advanced Installer Settings, set TT = OA. This
configures the thermostat to receive the outdoor
temperature information. High and low balance
point settings are also set in the Advanced
Installer Settings.
HB = 55 is the factory default high balance point
setting and LB = 35 is the factory default low
balance point setting in degrees Fahrenheit. High
balance point is adjustable from 32° F to 122° F
and low balance point is adjustable from 15° F to
77° F.
Switch 2 sets the equipment
configuration. For heat / cool
equipment, set the switch to the OFF
position (factory default). For heat
pump equipment, set the switch
to the ON position.
Sw3 - Equipment Stages
Switch 3 sets the equipment stages.
For single stage equipment, set the
switch to the OFF position (factory
default). For multi-stage equipment,
set the switch to the ON position.
Sw4 - Fan Mode or Reversing Valve
Switch 4 sets the fan logic for heat / cool
systems or sets the reversing valve
configuration for heat pump systems.
Fan Mode - For gas or oil systems
(equipment controls fan in heating mode),
set the switch to the OFF position (factory
default). For electric systems (thermostat
controls fan in heating mode), set the switch
to the ON position.
It is very important that the W2 relay be
configured to lock out the heat pump on low
balance point or whenever the thermostat calls
for auxiliary or emergency heat. In the
Advanced Installer Settings, set H3 = FF.
Reversing Valve - For ‘O’ reversing valve
(energize in cooling), set the switch to the
OFF position (factory default). For ‘B’
reversing valve (energize in heating), set the
switch to the ON position.
ACTIVATING THE BATTERY
Sw5 - Short Cycle Timer
The T-32-P2 contains a 3
REMOVE TAB
Leave switch 5 ON for 4 minute short cycle
protection (factory default).
volt
Lithium cell battery that
maintains the time of day in
the event of a power failure.
To activate the battery,
carefully remove the white
tab.
Sw6 - Thermostat Operation
ON
1 2 3 4 5 6 7 8
Switch 6 sets the thermostat operation.
For programmable, set the switch in the
ON position (factory default).
For non-programmable, set the switch
in the OFF position.
. . . . . . . . . . . .
Sw7 - Minimum Run Time
F
I
G
U
R
E
4
Leave switch 7 to OFF for 2 minute minimum
run time (factory default).
Sw8 - Program Schedule
Leave switch 8 to ON for separate heating
and cooling setpoints (factory default).
SETTING THE SYSTEM SWITCHES
The T-32-P2 contains a set
of eight system switches
located on the thermostat
FACTORY DEFAULT SETTINGS
ON
printed circuit board. The
1 2 3 4 5 6 7 8
SWITCH
1 - Fan
ON/OFF
OFF
FUNCTION
Fan Relay
Heat / Cool
1 Stage
switches are used to match
the thermostat with the
specific type of HVAC
system and user
preferences. Refer to the
2 - Equipment
3 - Stages
OFF
. . . . . . . . . . . .
FIGURE 5
OFF
system switch functions to
properly configure the
thermostat.
4 - Fan Mode /
Reversing Valve
OFF
Equipment Controls Fan /
‘O’ Reversing Valve
5 - Short Cycle Timer
6 - Operation
ON
4 Minute Short Cycle Protection
(Figure 5)
OFF
OFF
ON
Manual
7 - Minimum Run Time
8 - Setpoints
2 Minutes
Leave switch 8 to ON for
separate heating and
cooling setpoints.
6
| General | Details |
|---|---|
| Name | iO HVAC Controls T-32-P2 Universal Thermostat Instruction Manual |
| Make | iO HVAC Controls |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.36 MB |