Dec Hex  
Value  
range  
Access  
Description  
Means  
Default  
50  
Fan on temperature for heating  
The fan will start working if the temperature  
in the room drops below the preset  
by the value of the parameter  
241 0x00F1 R/W (#06)  
242 0x00F2 R/W (#06)  
0 - 50  
N-> temp=N/10 °C  
(Installer parameters -P11  
0 = TPI  
1 = 0,1C  
2 = 0,2C...  
Control algorithm  
(TPI or hysteresis) for the heating valve  
(Installer parameters -P12)  
0 - 20  
5
N-> temp=N/10 °C ( 0,1... 2C)  
FAN delta algorithm for cooling  
The parameter determines the width of the temperature  
range in which the fan operates in cooling mode.  
If the room temperature increases then:  
1. when a small value of Delta FAN,  
the faster the response of the fan to a change in  
temperature  
243 0x00F3 R/W (#06)  
5 - 50  
N-> temp=N/10 °C  
20  
temperature - faster increase in speed.  
2. when large value of Delta FAN,  
the slower the fan increases speed.  
(Installer parameters -P13)  
Fan on temperature for cooling.  
The fan will start working if the temperature  
in the room rises above the  
the setpoint by the value of the parameter.  
(Installer parameters -P14)  
244 0x00F4 R/W (#06)  
245 0x00F5 R/W (#06)  
0 - 50  
1 - 20  
N-> temp=N/10 °C  
50  
5
Hysteresis value for the cooling valve  
(Installer parameters -P15)  
N-> temp=N/10 °C ( 0,1... 2C)  
Dead zone of switching heating/cooling  
In a 4-pipe system.The difference between the  
Set temperature and room temperature,  
at which the controller will automatically change the  
heating/cooling operation mode.  
246 0x00F6 R/W (#06)  
247 0x00F7 R/W (#06)  
248 0x00F8 R/W (#06)  
5 - 50  
N-> temp=N/10 °C  
N-> temp=N/10 °C  
N-> temp=N/10 °C  
20  
(Installer parameters -P16)  
The switching temperature value from heating to cooling  
- 2-pipe system.  
In a 2-pipe system, below this value the  
system switches to cooling mode  
and allows the fan to start.  
270 - 400  
300  
100  
(Installer parameters -P17)  
The value of the switching temperature from cooling  
into heating - 2-pipe system.  
In a 2-pipe system, above this value the  
system switches to heating mode  
and allows the fan to start.  
100 - 250  
(Installer parameters -P18)  
Cooling ON delay.  
A parameter used in 4-pipe systems with automatic  
switching between heating and cooling.  
This avoids too frequent switching between heating and  
cooling modes and oscillation of the room temperature.  
(Installer parameters -P19)  
249 0x00F9 R/W (#06)  
0 - 15 min  
0
Maximum floor temperature  
To protect the floor, heating will be turned off,  
when the floor sensor temperature rises  
above the maximum value.  
250 0x00FA R/W (#06)  
50 - 450  
N-> temp=N/10 °C  
350  
(Installer parameters -P20)  
4
GeneralDetails
NameEngo EFAN-230 Zigbee Smart Thermostat Owner’s Manual
MakeENGO
LanguageEnglish
FiletypePDF (Download)
File size0.12 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
ENGO E55W230WIFI Wi-Fi Thermostat User Guide
ENGO E55W230WIFI Wi-Fi Thermostat User Guide
ENGO E20i Series Wi-Fi Wireless Internet Thermostat User Guide
ENGO E20i Series Wi-Fi Wireless Internet Thermostat User Guide
ENGO EONEBATW, EONEBATB Internet Controlled Thermostat User Guide
ENGO EONEBATW, EONEBATB Internet Controlled Thermostat User Guide
ENGO E901 Programmable Wired Thermostat User Manual
ENGO E901 Programmable Wired Thermostat User Manual
ENGO E901 Wireless Internet Thermostat User Manual
ENGO E901 Wireless Internet Thermostat User Manual
ENGO EASY230W Wired Thermostat User Guide
ENGO EASY230W Wired Thermostat User Guide
ENGO EASYBATB Wired Battery Thermostat User Guide
ENGO EASYBATB Wired Battery Thermostat User Guide

Engo EFAN-230 Zigbee Smart Thermostat Owner’s Manual