Engo EFAN-230 Zigbee Smart Thermostat Owner’s Manual
Adress
Dec Hex
Value
range
Access
Description
Means
Default
50
Fan on temperature for heating
The fan will start working if the temperature
in the room drops below the preset
by the value of the parameter
241 0x00F1 R/W (#06)
242 0x00F2 R/W (#06)
0 - 50
N-> temp=N/10 °C
(Installer parameters -P11
0 = TPI
1 = 0,1C
2 = 0,2C...
Control algorithm
(TPI or hysteresis) for the heating valve
(Installer parameters -P12)
0 - 20
5
N-> temp=N/10 °C ( 0,1... 2C)
FAN delta algorithm for cooling
The parameter determines the width of the temperature
range in which the fan operates in cooling mode.
If the room temperature increases then:
1. when a small value of Delta FAN,
the faster the response of the fan to a change in
temperature
243 0x00F3 R/W (#06)
5 - 50
N-> temp=N/10 °C
20
temperature - faster increase in speed.
2. when large value of Delta FAN,
the slower the fan increases speed.
(Installer parameters -P13)
Fan on temperature for cooling.
The fan will start working if the temperature
in the room rises above the
the setpoint by the value of the parameter.
(Installer parameters -P14)
244 0x00F4 R/W (#06)
245 0x00F5 R/W (#06)
0 - 50
1 - 20
N-> temp=N/10 °C
50
5
Hysteresis value for the cooling valve
(Installer parameters -P15)
N-> temp=N/10 °C ( 0,1... 2C)
Dead zone of switching heating/cooling
In a 4-pipe system.The difference between the
Set temperature and room temperature,
at which the controller will automatically change the
heating/cooling operation mode.
246 0x00F6 R/W (#06)
247 0x00F7 R/W (#06)
248 0x00F8 R/W (#06)
5 - 50
N-> temp=N/10 °C
N-> temp=N/10 °C
N-> temp=N/10 °C
20
(Installer parameters -P16)
The switching temperature value from heating to cooling
- 2-pipe system.
In a 2-pipe system, below this value the
system switches to cooling mode
and allows the fan to start.
270 - 400
300
100
(Installer parameters -P17)
The value of the switching temperature from cooling
into heating - 2-pipe system.
In a 2-pipe system, above this value the
system switches to heating mode
and allows the fan to start.
100 - 250
(Installer parameters -P18)
Cooling ON delay.
A parameter used in 4-pipe systems with automatic
switching between heating and cooling.
This avoids too frequent switching between heating and
cooling modes and oscillation of the room temperature.
(Installer parameters -P19)
249 0x00F9 R/W (#06)
0 - 15 min
0
Maximum floor temperature
To protect the floor, heating will be turned off,
when the floor sensor temperature rises
above the maximum value.
250 0x00FA R/W (#06)
50 - 450
N-> temp=N/10 °C
350
(Installer parameters -P20)
4
| General | Details |
|---|---|
| Name | Engo EFAN-230 Zigbee Smart Thermostat Owner’s Manual |
| Make | ENGO |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.12 MB |

ENGO E55W230WIFI Wi-Fi Thermostat User Guide

ENGO E20i Series Wi-Fi Wireless Internet Thermostat User Guide

ENGO EONEBATW, EONEBATB Internet Controlled Thermostat User Guide

ENGO E901 Programmable Wired Thermostat User Manual

ENGO E901 Wireless Internet Thermostat User Manual

ENGO EASY230W Wired Thermostat User Guide

ENGO EASYBATB Wired Battery Thermostat User Guide