HOLDING registers – for reading and writing  
Adress  
Value  
range  
Access  
Description  
Means  
Default  
1
Dec  
0
Hex  
0x0000 R/W (#04)  
Engo MODBUS Model ID  
1-247 MODBUS Slave (ID)  
1 = 2 pipe - only heating  
2 = 2 pipe - only cooling  
3 = 2 pipe - heating & cooling  
4 = 2 pipe - underfloor heating  
5 = 4 pipe - heating & cooling  
234 0x00EA R/W (#06)  
Fancoil type  
1 - 6  
0
6 = 4 pipe - underfloor heating & cooling by fancoil  
Input inactive. Change between heating  
and cooling with the buttons.  
0
1
Input used to change heating/cooling via external contact  
connected to S1-COM:  
- S1-COM open --> HEAT mode  
- S1-COM shorted --> COOL mode  
Input used to AUTOMATICALLY change heating/cooling  
based on PIPE TEMPERATURE in a 2-pipe system.  
The controller switches between heating  
and cooling modes based on the pipe temperature set  
in parameters P17 and P18.  
2
3
S1-COM input configuration  
(P01 install parameter)  
235 0x00EB R/W (#06)  
0
Allow fan operation dependent on the temperature  
measurement on the pipe. For example, if the temperature  
on the pipe is too low, and the controller is in heating mode  
- the pipe sensor will not allow the fan to run.  
The change of heating/cooling is done manually - using the  
buttons. Values for fan control based on pipe temperature  
are set in parameters P17 and P18.  
Activation of the floor sensor in the floor heating  
configuration.  
4
0
1
Input disabled  
S2-COM input configuration  
(P02 install parameter)  
Occupancy sensor (when contacts are opened, activate ECO  
mode)  
236 0x00EC R/W (#06)  
237 0x00ED R/W (#06)  
0
0
2
0
1
External temperature sensor  
NO - Disabled  
Selectable ECO mode  
(Installer Parameters -P07)  
YES - Active  
ECO mode temperature value for heating  
(Installer parameters -P08)  
238 0x00EE R/W (#06)  
239 0x00EF R/W (#06)  
50 - 450  
50 - 450  
N-> temp=N/10 °C  
N-> temp=N/10 °C  
150  
300  
ECO mode temperature value for cooling  
(Installer parameters -P09)  
Algorithm delta FAN in heating mode  
The parameter determines the width of the temperature  
range,  
in which the fan operates in heating mode.  
If the room temperature drops then:  
240 0x00F0 R/W (#06) 1. when the value of delta FAN is small, the faster the  
response of the fan to a change in temperature  
- faster increase in speed  
5 - 50  
N-> temp=N/10 °C  
20  
2. when high value of Delta FAN,  
the slower the fan increases speed  
(Installer parameters -P10)  
3
GeneralDetails
NameEngo EFAN-230 Zigbee Smart Thermostat Owner’s Manual
MakeENGO
LanguageEnglish
FiletypePDF (Download)
File size0.12 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
ENGO E55W230WIFI Wi-Fi Thermostat User Guide
ENGO E55W230WIFI Wi-Fi Thermostat User Guide
ENGO E20i Series Wi-Fi Wireless Internet Thermostat User Guide
ENGO E20i Series Wi-Fi Wireless Internet Thermostat User Guide
ENGO EONEBATW, EONEBATB Internet Controlled Thermostat User Guide
ENGO EONEBATW, EONEBATB Internet Controlled Thermostat User Guide
ENGO E901 Programmable Wired Thermostat User Manual
ENGO E901 Programmable Wired Thermostat User Manual
ENGO E901 Wireless Internet Thermostat User Manual
ENGO E901 Wireless Internet Thermostat User Manual
ENGO EASY230W Wired Thermostat User Guide
ENGO EASY230W Wired Thermostat User Guide
ENGO EASYBATB Wired Battery Thermostat User Guide
ENGO EASYBATB Wired Battery Thermostat User Guide

Engo EFAN-230 Zigbee Smart Thermostat Owner’s Manual