INSTALLER/CONFIGURATION MENU  
ditioner would need to run continuously for 1 ½ hours). The  
offset is limited to the number of degrees you select from  
1 up to 6. When an offset starts or is active, “Cool Savings”  
will flash on the display.  
The principle of this energy saving feature takes advantage  
of the long air conditioning run times lowering the indoor  
humidity allowing a slightly higher temperature to feel  
comfortable. As the peak load subsides, this feature also  
takes advantage of the air conditioner's increased capacity  
12. Select Compressor Lockout (CL) – Selecting (CL On)  
will cause the thermostat to wait 5 minutes between cool-  
ing cycles. This is intended to help protect the compressor  
from short cycling. Some of the newer compressors have  
a time delay built in and do not require this feature to be  
activated in the thermostat.Your compressor manufactur-  
er can tell you if this lockout feature is already present in  
their system. When the thermostat compressor time delay  
is activated, it will flash the set point for up to five minutes.  
13. Select Continuous Display Lighting (dL) -  
In low lighting conditions, display backlight  
improves the display contrast. (See Table 1)  
Power Stealing Switches ON  
(Factory Default)  
Power Stealing Switches ON  
(Factory Default)  
Backlight Option  
ON  
Backlight Option  
Backlight Option  
Backlight Option  
OFF  
OFF  
(Factory Default)  
ON  
Momentary  
Backlight  
(Factory Default)  
Power Method  
Battery Only (before thermostat installation or  
mV heat systems)  
No Backlight  
Momentary Backlight  
No Backlight  
Common Attached to "C" Terminal  
Momentary Backlight  
Momentary Backlight*  
No Backlight*  
Continuous Backlight  
Momentary Backlight  
No Backlight  
Continuous Backlight  
Continuous  
Backlight*  
Momentary  
Backlight  
Battery with Power Stealing on "W/E" and "Y"  
Battery with "W/E" and "Y" but system does not allow  
Power Stealing*  
Momentary  
Backlight*  
Momentary  
Backlight  
No Backlight  
* Power Stealing Backlight Notes:  
•฀ If the sysrem is heat or cool only, or does not allow  
•฀ of the thermostat are set to off the backlight will not be  
continous.  
power stealing on the thermostat terminals W/E and •฀ The display light will increase in brightness when a  
Y the backlight may not operate continously or drop out  
when heat or cool is running.  
•฀ If the power stealing switches (see page 2) on the back  
button is pressed.  
•฀ On high impedance systems, the display light may dim  
slightly when the thermostat is calling for heat or cool.  
14. Select Temperature Display Adjustment 5 LO to 5 HI  
This allows you to adjust the room temperature display  
by -5°F to +5°F in 1° steps.Your thermostat was accu-  
rately calibrated at the factory, however you have the  
option to change the display temperature value to match  
the previous thermostat, if you so prefer.  
15. Select °F or °C Readout – Changes the display readout  
to Celsius or Fahrenheit as required.  
16. Select Audio Prompting (Beeper) On or Off – Factory  
default setting is b, On. If you wish to turn off the beeper  
select OFF.  
17. Select Daylight Saving Time Calculation – This feature  
will allow the thermostat to calculate the DST automatically  
and apply it to the Real Time Clock display. Default is On.  
18 & 19. Select Automatic Schedule – Not available if  
configured for non-programmable. This feature allows  
programming a “Comfort Temperature” into all program  
periods with the Auto Schedule key. When Heat AS  
(for Heat mode) or Cool AS (for Cool mode) is selected  
On, the Auto Schedule feature is ready to be set. Off  
indicates that the feature is not ready to be used or a  
“Comfort Temperature" is already set. See Auto Schedule  
in Programming section.  
20 & 21. Select Cool Savings™ – Cool Savings™ provides an  
energy saving temperature offset (from 1-6 degrees) under  
peak cooling load conditions (high outdoor temperatures).  
If selected on, Cool Savings™ becomes active when the  
air-conditioner runs for periods of longer than 20 minutes.  
When active, Cool Savings™ gradually offsets the indoor  
temperature display downward. The first 1° of adjustment  
will take one hour of continuous air conditioner run time  
with subsequent 1° adjustments occurring with each ad-  
ditional half hour of run time (ex for a 2° offset, the air con-  
under more efficient conditions to gradually reduce the off-  
set back to zero and return control to the selected setpoint  
temperature.  
If Cool Savings is selected off, no temperature offset  
will occur.  
22. Compressor Optimization – (Not available on earlier  
models) CO provides a delay in circulator fan operation  
after the compressor turns on or off. With CO selected  
ON, when the compressor turns on (for a call for heat  
in heat pump or a call for cool) the fan will be delayed  
for five seconds before turning on to allow the air to be  
heated or cooled. After the compressor turns off for call  
for cool, the fan will continue to run for 20 seconds to  
capture additional cooling from the system. If CO is set to  
OFF, there will be no delay in fan operation.  
23. Comfort Alert with Active Protection – (not available  
on earlier models) Turn this feature ON to enable active  
protection. This allows the thermostat to identify fault  
codes sent by the Comfort Alert module when compres-  
sor damage is possible and react to those codes by  
turning the compressor off. Fault codes from the Comfort  
Alert module will flash on the thermostat. (Refer to Com-  
fort Alert Codes in Troubleshooting section.) If a Comfort  
Alert module is not connected, or to disable active protec-  
tion, turn this feature OFF. If a Comfort Alert module is  
connected and this feature is turned OFF, the thermostat  
will still receive and flash the fault codes from the Comfort  
Alert module, but the active protection will not be enabled  
to protect the compressor.  
24. Heat Temperature Limit Range – This feature adjusts  
the highest setpoint temperature for heat. The default set-  
ting is 99°F. It can be changed to a setting between 62°F  
and 98°F. The "temperature limit" icon will be displayed  
8
GeneralDetails
NameCOPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual
MakeCopeland
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND ST55 Sensi Smart Thermostat Instruction Manual
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual
COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual
COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual

COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual