COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual
WIRING DIAGRAMS
Optional Jumper for
Single Stage Heat Pump
THERMOSTAT
SYSTEM
R
O/B
Y
G
W
C
Changeover
Relay*
Fan
Optional
Compressor
Contactor
Relay
Heat Relay
Hot
24 VAC
120 VAC
Neutral
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
TRANSFORMER
(Class II Current Limited)
Figure 2.Typical wiring diagram for single transformer single stage systems
NOTE
If safety circuits are in
only one of the systems,
remove the transformer
of the system with NO
safety circuits.
Optional Jumper for
Single Stage Heat Pump
THERMOSTAT
SYSTEM
O/B
Y
G
W
C
R
CUT AND
TAPE OFF!
Changeover
Relay*
Fan
Limit or
Safety
Switches
Optional
Relay
HOT
120 VAC
24 VAC
Compressor
Contactor
Heat Relay
NEUTRAL
Hot
24 VAC
120 VAC
Neutral
TWO COMMONS MUST
BE JUMPERED TOGETHER!
TRANSFORMER
(Class II Current Limited)
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
Figure 3.Typical wiring diagram for two transformer single stage systems with NO safety circuits
NOTE
Polarity must be observed. If the HOT side of the
second transformer is jumpered to the COMMON side
of the first transformer a short will be made. Damage
Optional Jumper for
Single Stage Heat Pump
to equipment will occur when power is restored.
THERMOSTAT
O/B
Y
G
W
C
R
SYSTEM
Limit or
Safety
Switches
Limit or
Safety
Switches
HOT
24 VAC
120 VAC
Changeover
Relay*
Fan
NEUTRAL
Optional
Relay
24 VAC
Auxiliary
Heating
Transformer
(Class II
Current Limited)
NOTE
ACCESSORY
RELAY N.O.
CONTACT
The accessory relay scheme
is required when safety
circuits exist in both systems.
Compressor
Contactor
Heat
Relay
COMMON
TWO COMMONS MUST
BE JUMPERED TOGETHER!
Limit or
Safety
Switches
Limit or
Safety
Switches
HOT
24 VAC
120 VAC
COMMON
NEUTRAL
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
Heat Pump Transformer
(Class II Current Limited)
Figure 4.Typical wiring diagram for two transformer single stage systems with safety circuits in BOTH systems
3
| General | Details |
|---|---|
| Name | COPELAND 1F86-0244 Blue 2 Inch Single Stage Thermostat Instruction Manual |
| Make | Copeland |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.34 MB |

COPELAND 1F95G-1235GC Humidity Universal Thermostat Instruction Manual

COPELAND ST55 Sensi Smart Thermostat Instruction Manual

COPELAND 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide

COPELAND 026-1739 Programmable Touchscreen Thermostat User Manual

COPELAND P-N 810-1600 Programmable Touchscreen Thermostat User Guide