Honeywell TH5220D1003 Heater Thermostat Owner’s Manual
6-436.9
5H76292A
August, 2009
Honeywell TH5220D1003 thermostat wiring for gas
unit heaters HD/HDB, HDS/HDC, PTS/BTS, PTC, PDP/BDP, and
duct furnaces “D”, “H”, “I”, & “O” series
WARNING
1. Disconnect power supply before making wiring connections
to prevent electrical shock and equipment damage.
2. All units must be wired strictly in accordance with wiring
diagram furnished with the unit. Any wiring different from
the wiring diagram could result in a hazard to persons and
property.
3. All wiring must be done with a wiring material having a
temperature rating of at least 105°C.
Wiring Diagram Selection
IMPORTANT
• For gas fired unit heaters and duct furnaces (non-factory
1. The use of this manual is specifically intended for a
supplied blower) with model numbers shown above, refer to
qualified installation and service agency. All installation
Figure 1.1 and Table 1.1 for correct unit to thermostat wiring.
and service of these kits must be performed by a qualified
installation and service agency.
2. These instructions must also be used in conjunction with
the Installation and Service Manual that originally shipped
with the appliance, in addition to any other accompanying
component supplier literature.
• For all other system units (factory supplied blower), refer to
the job specific unit wiring diagram provided with the unit.
• For deviations to these wiring diagrams or the job specific
wiring diagrams, consult the factory.
Figure 1.1 - Terminals on Thermostat
Installation and Wiring
Installation of wiring must conform with local building codes,
or in the absence of local codes of the National Electric Code
ANSI/NFPA 70 - Latest Edition. Unit must be electrically
grounded in conformance to this code. In Canada, wiring must
comply with CSA C22.1, Part 1, Electrical Code.
Table 1.1 - Thermostat to Unit Wiring
Wiring Terminals on Thermostat
Location of Unit
Terminals
Model
W2
G
W
C
R
(2-stage ONLY)
HD/HDB, HDS/HDC,
PTS/BTS
Ignition control in unit
control compartment
W2
n/a
G
W1
C
R
Terminal board on
external junction box
PTC
G
F
T2
T2
F
T1
T1
Gas valve high stage
(HI, 3, or A)
Terminal board on
external junction box
PDP/BDP
G
Fan relay by others or to
factory relay wire removed
from T or H
Terminal board on
external junction box
(Digit 13=4 Only)
Gas valve high stage
(HI, 3, or A)
DFG, IFG, DFP, IFP
T
4
G
2
H
1
Terminal strip in control
compartment (Digit
13=0, 1, 2, or 3)
DFG, IFG, DFP, IFP, DFS,
IFS, HFG, OFG, HFP, OFP
Factory time delay relay
wire removed from 4
3
➀ Not all terminal connections are used. Table only shows terminals that are used for required heating operation.
➁ The factory installed R to Rc terminal wire jumper is to remain in place.
➂Verify that the buss bar on the G terminal is removed.
➃ Verify that the buss bar between the T2 and F terminal is removed.
(See page 2 for Thermostat Function Programming Instructions)
firealarmresources.com
| General | Details |
|---|---|
| Name | Honeywell TH5220D1003 Heater Thermostat Owner’s Manual |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.1 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell D1-528 Direct Thermostat Installation Guide

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell TH5220D1003 Heater Thermostat Owner’s Manual Overview
Summary of Contents
- Page 1: Honeywell TH5220D1003 thermostat wiring for gas unit heaters and duct furnaces. WARNING: Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage. All units must be wired strictly in accordance with the wiring diagram furnished with the unit. Wiring must be done with a wiring material having a temperature rating of at least 105°C. Installation of wiring must conform with local building codes or the National Electric Code ANSI/NFPA 70 - Latest Edition. For gas fired unit heaters and duct furnaces, refer to the provided wiring diagram for correct unit to thermostat wiring. These instructions must be used in conjunction with the Installation and Service Manual that originally shipped with the appliance. For deviations to these wiring diagrams, consult the factory. Verify that the buss bar on the G terminal is removed. The factory installed R to Rc terminal wire jumper is to remain in place.
- Page 2: Programming mode allows entry into thermostat setup. To enter setup mode, press and hold the s and FAN buttons until the display changes. Use the s and t buttons to change settings, the NEXT button to advance, and the DONE button to save and exit. Refer to Table 2.1 for typical thermostat function settings for gas fired unit heaters and duct furnaces. Consult the factory for deviations to wiring diagrams. Refer to vendor literature for additional information on the thermostat. Typical settings include single stage heat only with fan and various configurations for gas or oil furnaces. Cooling functions and temperature range stops are also specified. Default values can be adjusted within specified ranges. Refer to Honeywell instructions for more information and additional setting options.