The setting options are shown in the table below:
Display
DIF
Function
Setting Options
±0.1 – ±1.0 °C
Default Setting
±0.2 °C
Detailed Description
Chapter 11.1.
Selecting switching sensitivity
SVH
SVL
ADJ
Defining maximum settable temperature
Defining minimum settable temperature
Calibration of the temperature sensor
5 – 99 °C
5 – 99 °C
-3 – +3 °C
35 °C
5 °C
----
----
0.0 °C
Chapter 11.2.
00: OFF
01: ON
00: OFF
01: ON
FRE
PON
Antifreezing
00
01
Chapter 11.3.
Chapter 11.4.
Memorizing ON/OFF status in case of a
power failture
01: only On/Off button works
02: all buttons locked
LOC
FUN
SNP
Setting the keylock funcion
Changing between heating or cooling mode
Synchronization with a receiver unit
02
00
00
----
00: heating
01: cooling
Chapter 11.5.
Chapter 7.3.
00: disable synchronization
01: enable synchronization
00: Resetting to factory default
08: saving settings
FAC
----
Resetting to factory default
Delay of receiver unit outputs
08
Chapter 11.6.
Chapter 11.7.
----
turned off
11.1. Selecting the switching sensitivity (DIF)
It is possible to set the switching sensitivity. By setting this value, you can specify how much the appliance
switches the connected device on/off below/above the set temperature.
The lower this value, the more uniform the internal temperature of the room, the greater the comfort will be.
The switching sensitivity does not affect the heat loss of the room (building).
- 25 -
| General | Details |
|---|---|
| Name | COMPUTHERM E800RF Multizone Wi-Fi Thermostat Instruction Manual |
| Make | COMPUTHERM |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.03 MB |

COMPUTHERM Q20 Programmable Digital Room Thermostat Instruction Manual
COMPUTHERM Q5RF Multi Zone Wireless Digital Room Thermostat Instruction Manual